FIR08-00300
| INSP-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 4:27:24 PM | A | NR |
|
|
Reschedule for tomorrow, with fire alarm inspection. KR
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 6/27/2008 | 6/30/2008 | 6/30/2008 4:13:16 PM | P | PART |
|
|
Inspection for the 5th floor OH rough-in only completed today, see 6 item list on approved plan set including seismic clearance, plumbing pipe supported by sprinkler pipe, be aware of possible light fixture obstructions, discussed relocation of one sw head at the west end unit, provide as-builts for minor field modifications/floor plan changes, rotate one sw head to vertical, standpipe needs proper seismic clearance or flex couplings within 1' on either side, discussed hydrostatic testing schedule for overhead work.
|
BLD08-00786
| FIRE-Final Inspection | 6/30/2008 | 6/30/2008 | 6/30/2008 4:07:23 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD08-00787
| FIRE-Final Inspection | 6/30/2008 | 6/30/2008 | 6/30/2008 4:06:55 PM | P | PASS |
|
|
Fire life safety inspection passed-per Forrest France Fir08-00399 covers Elam & Burke and vanilla finish///7-2-08 BAS
|
FIR08-00068
| INSP-Sprinkler Rough-in | 6/27/2008 | 6/30/2008 | 6/30/2008 2:38:29 PM | A | FAIL |
|
|
See annotations on plan for areas in need of revision including missing head coverage at a storage room, two missing armover hangers, three painted heads to be replaced, and one pendent cut too high. Remainder of overhead system modifications are good for cover at the drop ceilings.
|
FIR08-00312
| INSP-Alarm Testing | 6/27/2008 | 6/30/2008 | 6/30/2008 1:10:30 PM | P | CANC |
|
|
Talked with David and let him know that the sprinkler permit also needs to be called in for the fire alarm testing. He will call in both permits tomorrow for finals.KR
|
BLD07-02588
| FIRE-Final Inspection | 6/26/2008 | 6/30/2008 | 6/30/2008 12:59:47 PM | A | PASS |
|
|
Life safety passed. KR
|
BLD08-00705
| FIRE-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 12:40:58 PM | A | PASS |
|
|
Fire life safety passed, fire sprinkler permit not required as no modifications necessary, noted door is not yet installed-verified hardware will be compliant per contractor.
|
FIR08-00394
| INSP-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 12:34:53 PM | A | PASS |
|
|
Fire alarm test completed.KR
|
FIR08-00047
| INSP-Final Inspection | 6/30/2008 | 6/30/2008 | 6/30/2008 12:00:42 PM | P | PART |
|
|
Temp. okayed with D. Hanneman's permission pending completion of the elevator controls-no elevator use allowed until upgrade work is finished, tested and related fire alarm permit finaled.
|
FIR08-00385
| INSP-Sprinkler Rough-in | 6/30/2008 | 6/30/2008 | 6/30/2008 11:57:57 AM | P | PART |
|
|
OH fire sprinkler modifications are good for cover at the file storage room, C/N items verified for compliance.
|
BLD07-01932
| FIRE-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 11:56:07 AM | A | PART |
|
|
Okay for temporary occupancy with D. Hanneman's permission pending completion of the elevator controls. NOTE: elevator power to be turned off and no use is allowed until work is completed and tested per Temporary Occ. conditions and agreement.
|
FIR08-00450
| INSP-Final Inspection | 6/30/2008 | 6/30/2008 | 6/30/2008 11:43:58 AM | P | PASS |
|
|
Noted corrections are complete, final fire alarm testing passed, permit finaled.
|
BLD07-00133
| FIRE-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 11:42:01 AM | A | NR |
|
|
Missing ceiling tile at several locations, project related fire sprinkler permit needs finaled, not ready for final fire life safety approval at this time.
|
BLD07-03107
| FIRE-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 11:40:18 AM | A | FAIL |
|
|
Missing project related fire sprinkler permit final.
|
BLD08-00882
| FIRE-Final Inspection | 6/27/2008 | 6/30/2008 | 6/30/2008 11:36:31 AM | A | PASS |
|
|
Door hardware changed per Forrest last inspection. KR
|
FIR08-00182
| INSP-Sprinkler Rough-in | 6/27/2008 | 6/30/2008 | 6/30/2008 8:44:48 AM | P | CANC |
|
|
UG Flush Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR08-00093
| INSP-Final Inspection | 6/30/2008 | 6/30/2008 | 6/30/2008 12:00:00 AM | A | PASS |
|
|
Fire alarm testing completed.KR
|