BLD09-01453
| BLD-Aging Inspection | 6/30/2010 | 6/30/2010 | 7/2/2010 3:33:57 PM | P | NR |
|
|
I stopped at the job site and spoke to Meg. She said there were a few more items needing to be addressed and then they would call in the inspection.
|
FIR09-00342
| INSP-Final Inspection | 6/30/2010 | 6/30/2010 | 7/1/2010 1:15:22 PM | P | FAIL |
|
|
There is no independant supervisory signal being reported. The existing facp is capable of this function per the Pyrotronics vendor. This capability will need to be installed and tested prior to a final sign off. The technician and I discussed the issue.
|
FIR09-00277
| INSP-Final Inspection | 6/30/2010 | 6/30/2010 | 6/30/2010 4:45:56 PM | P | FAIL |
|
|
The model of Aes installed does not match what was submitted. Also an intella tap has been installed which is not shown on the plans. I told Randy that this once I would accept this as an as-built but all other would need to resubmitted as previously discussed on the last inspection.
|
BLD10-01329
| FIRE-Final Inspection | 6/30/2010 | 6/30/2010 | 6/30/2010 4:42:19 PM | P | FAIL |
|
|
See the city approved plans for the deficiencies listed in red. They include providing correct door hardware on all of the exterior exit doors, repairing all of the exit signs/emergency lights and removing the non-functional fire alarm system.
|
FIR10-00022
| INSP-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 4:37:58 PM | A | PASS |
|
|
permit finaled
|
FIR08-00367
| INSP-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 12:34:20 PM | A | FAIL |
|
|
All previous items noted have been corrected except there is still the random horn sounding in the warehouse which will need to be corrected. Also as-builts are needed as previously requested that show the door mags, new duct smoke detectors, relocated duct detectors, adjusted candellas, relocated a/v's and new a/v's in the warehouse.
|
FIR09-00638
| INSP-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 12:28:25 PM | A | FAIL |
|
|
There were no approved drawings on site. The Netcon was verified at 5 and signals were received at the monitoring station. The wrong sized battery was installed as well.
|
BLD10-01423
| FIRE-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 11:57:34 AM | A | FAIL |
|
|
Provide sticker at the main exit and lever/single action on the north facing exterior exit door. See the city approved plans for redlines.
|
BLD06-01424
| FIRE-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 11:55:11 AM | A | PASS |
|
|
Life safety passed. Per Scott the fire hydrant was previously approved to be relocated from the position shown on the approved plans to the location near Emerald.
|
BLD10-00778
| FIRE-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 10:18:17 AM | A | PASS |
|
|
Life safety passed.
|
BLD10-01327
| FIRE-Final Inspection | 6/29/2010 | 6/30/2010 | 6/30/2010 8:32:29 AM | A | PASS |
|
|
Life safety passed. Deficiencies corrected from the previous correction notice.
|