Inspections for the day of: Wednesday, June 30, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-01453 BLD-Aging Inspection6/30/20106/30/20107/2/2010 3:33:57 PMPNR
I stopped at the job site and spoke to Meg. She said there were a few more items needing to be addressed and then they would call in the inspection.
FIR09-00342 INSP-Final Inspection6/30/20106/30/20107/1/2010 1:15:22 PMPFAIL
There is no independant supervisory signal being reported. The existing facp is capable of this function per the Pyrotronics vendor. This capability will need to be installed and tested prior to a final sign off. The technician and I discussed the issue.
FIR09-00277 INSP-Final Inspection6/30/20106/30/20106/30/2010 4:45:56 PMPFAIL
The model of Aes installed does not match what was submitted. Also an intella tap has been installed which is not shown on the plans. I told Randy that this once I would accept this as an as-built but all other would need to resubmitted as previously discussed on the last inspection.
BLD10-01329 FIRE-Final Inspection6/30/20106/30/20106/30/2010 4:42:19 PMPFAIL
See the city approved plans for the deficiencies listed in red. They include providing correct door hardware on all of the exterior exit doors, repairing all of the exit signs/emergency lights and removing the non-functional fire alarm system.
FIR10-00022 INSP-Final Inspection6/29/20106/30/20106/30/2010 4:37:58 PMAPASS
permit finaled
FIR08-00367 INSP-Final Inspection6/29/20106/30/20106/30/2010 12:34:20 PMAFAIL
All previous items noted have been corrected except there is still the random horn sounding in the warehouse which will need to be corrected. Also as-builts are needed as previously requested that show the door mags, new duct smoke detectors, relocated duct detectors, adjusted candellas, relocated a/v's and new a/v's in the warehouse.
FIR09-00638 INSP-Final Inspection6/29/20106/30/20106/30/2010 12:28:25 PMAFAIL
There were no approved drawings on site. The Netcon was verified at 5 and signals were received at the monitoring station. The wrong sized battery was installed as well.
BLD10-01423 FIRE-Final Inspection6/29/20106/30/20106/30/2010 11:57:34 AMAFAIL
Provide sticker at the main exit and lever/single action on the north facing exterior exit door. See the city approved plans for redlines.
BLD06-01424 FIRE-Final Inspection6/29/20106/30/20106/30/2010 11:55:11 AMAPASS
Life safety passed. Per Scott the fire hydrant was previously approved to be relocated from the position shown on the approved plans to the location near Emerald.
BLD10-00778 FIRE-Final Inspection6/29/20106/30/20106/30/2010 10:18:17 AMAPASS
Life safety passed.
BLD10-01327 FIRE-Final Inspection6/29/20106/30/20106/30/2010 8:32:29 AMAPASS
Life safety passed. Deficiencies corrected from the previous correction notice.