BLD11-01426
| FIRE-Final Inspection | 6/30/2011 | 6/30/2011 | 6/30/2011 5:38:06 PM | P | FAIL |
|
|
Noted items include; post premise identification as discussed, provide "door to remain unlocked.." signage at the main entry/exit, fire extinguishers must be posted on brackets/ hangers, exposed paper faced insulation must be concealed, ramp at the island per attatched drawing is not built.
|
BLD11-00300
| FIRE-Final Inspection | 6/29/2011 | 6/30/2011 | 6/30/2011 5:29:18 PM | P | FAIL |
|
|
Correction items include; repair two exit signs at the main entry vestibule area, provide approved hardware at the staff restroom door, replace missing ceiling tile at the electrical room next to the mens restroom, foam DP at the exisitng cooler, post fire extinguishers per plan and K class in the kitchen as discussed.
|
BLD11-00947
| FIRE-Final Inspection | 6/30/2011 | 6/30/2011 | 6/30/2011 5:24:58 PM | P | PASS |
|
|
Life safety completed acceptable with the exception of one EM light to be repaired prior to final.
|
FIR11-00256
| INSP-Final Inspection | 6/29/2011 | 6/30/2011 | 6/30/2011 5:23:56 PM | A | PASS |
|
|
Fire sprinkler permit finaled. Note: a portion of the drop ceiling will remain unfinished- upright protection throughout is provided, therefore coverage is adequate.
|
FIR11-00256
| INSP-Sprinkler Rough-in | 6/30/2011 | 6/30/2011 | 6/30/2011 5:21:09 PM | P | PART |
|
|
OH rough-in inspection passed.
|