BLD13-00938
| FIRE-Final Inspection | 6/26/2014 | 6/30/2014 | 7/1/2014 5:28:08 PM | P | FAIL |
|
|
Fire life safety inspection items for the 2nd, 3rd and 4th floor apartments completed 6/30 include; provide exit sign per plan review red line at the 1st floor landing east side stairway, install exit discharge lighting for both east and west stairways, test EM light 1st floor east stairway, remove scafolding in the west stairway, remove tape covering smoke alarms at 4th floor apartment units, install door seals at doors serving elevator lobbies to apt unit corridors, adjust closer at units 204, 206, 212. Remove tape and provide escutcheon at sprinkler head unit 206, provide intermediate temp pendent head at unit 312 adjacent to HVAC diffuser, install outside waterflow bell 11th street side, relocate two smoke alarms at unit 301, replace malfunctional flow switches at the 3rd and 4th floor sprinkler control manifolds. 1st floor fire sprinkler protection at the vacant shell does not meet NFPA 13 standards.
|
FIR13-00440
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 5:02:54 PM | P | PART |
|
|
Completed walkthrough for the 7th floor overhead finish work.
|
FIR14-00277
| INSP-Sprinkler Rough-in | 6/30/2014 | 6/30/2014 | 7/1/2014 5:00:08 PM | P | PART |
|
|
Remote FDC piping okayed for cover.
|
FIR13-00409
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 1:31:19 PM | P | PART |
|
|
Completed funcitional testing and inspection of fire alarm work at the 2nd, 3rd and 4th floor apartments and common corridors including notification and in-duct detectors. Also tested floor control manifolds for the 2nd, 3rd and 4th floor fire protection - tampers okayed, need to replace 3rd and 4th floor flow switches.
|
FIR13-00440
| INSP-Sprinkler Rough-in | 6/30/2014 | 6/30/2014 | 7/1/2014 1:27:26 PM | P | PART |
|
|
Terry-basement floor only please Phone #: ###-####
|
FIR13-00579
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 1:26:52 PM | P | PART |
|
|
Noted items on walkthrough of the 2nd, 3rd and 4th floor apartment units include taped head/missing escutcheon at unit 206, need to provide intermediate temp head at unit 312 adjacent to HVAC diffuser, flow switches at the 3rd and 4th floor are malfunctional, missing outside waterflow bell.
|
FIR14-00130
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 1:19:36 PM | P | PART |
|
|
Final pending plan modification for significant field changes to original layout.
|
FIR14-00241
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 1:18:07 PM | P | PASS |
|
|
Scope of work completed and passed final walkthrough.
|
FIR14-00231
| INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 1:17:06 PM | P | PART |
|
|
Scope of work is finished. Need to provide as builts for field modifications prior to final.
|
FIR14-00375
| INSP-Sprinkler Rough-in | 6/30/2014 | 6/30/2014 | 6/30/2014 3:06:26 PM | P | CANC |
|
|
Mike M is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR14-00277
| INSP-Sprinkler Rough-in | 6/30/2014 | 6/30/2014 | 6/30/2014 11:17:18 AM | A | NR |
|
|
Thrust blocking not yet finished per contractor.
|
BLD14-01271
| FIRE-Final Inspection | 6/27/2014 | 6/30/2014 | 6/30/2014 10:41:29 AM | A | PEND |
|
|
Doors and hardware incomplete at this time.
|
BLD14-01371
| FIRE-Final Inspection | 6/27/2014 | 6/30/2014 | 6/30/2014 10:01:49 AM | A | NR |
|
|
Not ready for final per conversation with contractor.
|
BLD11-00062
| FIRE-Final Inspection | 6/30/2014 | 6/30/2014 | 6/30/2014 10:00:31 AM | A | PASS |
|
|
Fire life safety finaled.
|
BLD11-00062
| BLD-Aging Inspection | 6/30/2014 | 6/30/2014 | 6/30/2014 10:00:02 AM | A | DONE |
|
|
Okayed for project final- Fire alarm work finished in coordination with FIR13-00682.
|
BLD14-00942
| FIRE-Final Inspection | 6/27/2014 | 6/30/2014 | 6/30/2014 9:44:48 AM | A | FAIL |
|
|
Need to provide current certification tags at both the main and second floor level fire extinguishers, remove storage and combustibles at the basement- to be used as mechanical room only.
|