Inspections for the day of: Monday, June 30, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00938 FIRE-Final Inspection6/26/20146/30/20147/1/2014 5:28:08 PMPFAIL
Fire life safety inspection items for the 2nd, 3rd and 4th floor apartments completed 6/30 include; provide exit sign per plan review red line at the 1st floor landing east side stairway, install exit discharge lighting for both east and west stairways, test EM light 1st floor east stairway, remove scafolding in the west stairway, remove tape covering smoke alarms at 4th floor apartment units, install door seals at doors serving elevator lobbies to apt unit corridors, adjust closer at units 204, 206, 212. Remove tape and provide escutcheon at sprinkler head unit 206, provide intermediate temp pendent head at unit 312 adjacent to HVAC diffuser, install outside waterflow bell 11th street side, relocate two smoke alarms at unit 301, replace malfunctional flow switches at the 3rd and 4th floor sprinkler control manifolds. 1st floor fire sprinkler protection at the vacant shell does not meet NFPA 13 standards.
FIR13-00440 INSP-Final Inspection6/30/20146/30/20147/1/2014 5:02:54 PMPPART
Completed walkthrough for the 7th floor overhead finish work.
FIR14-00277 INSP-Sprinkler Rough-in6/30/20146/30/20147/1/2014 5:00:08 PMPPART
Remote FDC piping okayed for cover.
FIR13-00409 INSP-Final Inspection6/30/20146/30/20147/1/2014 1:31:19 PMPPART
Completed funcitional testing and inspection of fire alarm work at the 2nd, 3rd and 4th floor apartments and common corridors including notification and in-duct detectors. Also tested floor control manifolds for the 2nd, 3rd and 4th floor fire protection - tampers okayed, need to replace 3rd and 4th floor flow switches.
FIR13-00440 INSP-Sprinkler Rough-in6/30/20146/30/20147/1/2014 1:27:26 PMPPART
Terry-basement floor only please Phone #: ###-####
FIR13-00579 INSP-Final Inspection6/30/20146/30/20147/1/2014 1:26:52 PMPPART
Noted items on walkthrough of the 2nd, 3rd and 4th floor apartment units include taped head/missing escutcheon at unit 206, need to provide intermediate temp head at unit 312 adjacent to HVAC diffuser, flow switches at the 3rd and 4th floor are malfunctional, missing outside waterflow bell.
FIR14-00130 INSP-Final Inspection6/30/20146/30/20147/1/2014 1:19:36 PMPPART
Final pending plan modification for significant field changes to original layout.
FIR14-00241 INSP-Final Inspection6/30/20146/30/20147/1/2014 1:18:07 PMPPASS
Scope of work completed and passed final walkthrough.
FIR14-00231 INSP-Final Inspection6/30/20146/30/20147/1/2014 1:17:06 PMPPART
Scope of work is finished. Need to provide as builts for field modifications prior to final.
FIR14-00375 INSP-Sprinkler Rough-in6/30/20146/30/20146/30/2014 3:06:26 PMPCANC
Mike M is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR14-00277 INSP-Sprinkler Rough-in6/30/20146/30/20146/30/2014 11:17:18 AMANR
Thrust blocking not yet finished per contractor.
BLD14-01271 FIRE-Final Inspection6/27/20146/30/20146/30/2014 10:41:29 AMAPEND
Doors and hardware incomplete at this time.
BLD14-01371 FIRE-Final Inspection6/27/20146/30/20146/30/2014 10:01:49 AMANR
Not ready for final per conversation with contractor.
BLD11-00062 FIRE-Final Inspection6/30/20146/30/20146/30/2014 10:00:31 AMAPASS
Fire life safety finaled.
BLD11-00062 BLD-Aging Inspection6/30/20146/30/20146/30/2014 10:00:02 AMADONE
Okayed for project final- Fire alarm work finished in coordination with FIR13-00682.
BLD14-00942 FIRE-Final Inspection6/27/20146/30/20146/30/2014 9:44:48 AMAFAIL
Need to provide current certification tags at both the main and second floor level fire extinguishers, remove storage and combustibles at the basement- to be used as mechanical room only.