Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00430 INSP-Sprinkler Rough-in6/29/20156/30/20156/30/2015 4:17:54 PMPPASS
Hydrostatic test of two Dry Pipe systems protecting the grade level parking garage - 200 psi @ 2 hours - PASSED
FIR14-00531 INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015 4:17:39 PMPPASS
Hydrotests of floors 2 and 4 - 200 psi @ 2hrs, - PASSED.
NOTE: Floor 3 had a leak and floor 5 is not ready for test.
FIR14-00531 INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015 4:15:31 PMPPASS
Hydrotests of floors 2 and 4 wet pipe systems - 200 psi @ 2hrs - PASSED
NOTE: Floor 3 had a leak, and floor 5 is not ready for test.
FIR14-00430 INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015 4:13:32 PMPPASS
Hydrotests of two (2) dry pipe systems protecting the grade level parking garage.
- 200 psi @ 2 hrs - PASSED
FIR14-00430 INSP-Sprinkler Rough-in/Hydro6/29/20156/30/20156/30/2015 2:54:55 PMPCANC
Wrong permit called in for this area. See FIR14-00531 for inspections completed today (6/30).
FIR14-00531 INSP-Sprinkler Rough-in6/30/20156/30/20156/30/2015 2:51:54 PMPPART
RTC inspection for under pool deck area - off of fitness room system.
OK to cover.
FIR13-00725 INSP-Sprinkler Rough-in6/30/20156/30/20156/30/2015 1:12:55 PMPPASS
Hydrotest of first fllor dry pipe system protecting A/G parking garage (around Helix). 200 psi @ 2 hours - PASSED
FIR13-00725 INSP-Sprinkler Rough-in6/29/20156/30/20156/30/2015 1:09:40 PMACANC
Wrong permit number for this inspection. See FIR13-00167 for FS U/G hydrotest inspection this date.
FIR13-00167 INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015 12:17:15 PMPPASS
Hydrostatic test of FS U/G supply line from 11th St. city connection to main BFP in basement riser room. PASSED
FIR13-00178 FIR-Aging Inspection6/30/20156/30/20156/30/2015 12:10:45 PM CANC
Wrong permit called in for this inspection. See FIR 13-00167 for hydrotest of U/G supply line (11th street connection).
FIR15-00096 INSP-Sprinkler Rough-in6/29/20156/30/20156/30/2015 10:31:45 AMACANC