Inspections for the day of: Tuesday, June 30, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01272 FIRE-Final Inspection6/29/20156/30/20156/30/2015 2:40:45 PMPPASS
Life fir safety passed/complete
FIR15-00156 INSP-Alarm Testing6/29/20156/30/20156/30/2015 2:27:41 PMPPASS
Fire alarm inspection passed/complete
BLD15-01075 FIRE-Final Inspection6/30/20156/30/20156/30/2015 12:50:33 PMPFAIL
Both exterior entry doors have thumb-turn deadbolt type lock assemblies, deadbolts need to be changed to single action locking hardware. One restroom, located in corridor attached to tenant space (Included in tenant scope of work) has thumb-turn deadbolt type lock assembly, deadbolt needs to be changed to single action locking hardware. No fire extinguisher in tenat space, instructed point of contact that fire extinguisher needs to be installed in tenatnt common area.
BLD15-01576 FIRE-Final Inspection6/29/20156/30/20156/30/2015 9:25:44 AMACANC
No inspection required.
BLD14-03175 FIRE-Final Inspection6/29/20156/30/20156/30/2015 9:10:18 AMPCANC
Inspection canceled per conversation with John Phone #: ###-####, superintendent of job, items on job need to be corrected/repaired before inspection can be performed.
FIR15-00185 INSP-Alarm Testing6/29/20156/30/20156/30/2015 8:32:08 AMAPART
Inspected/tested horns and strobes, 2nd floor and basement levels, both passed inspection. Activated newly installed pull station 2nd floor and basement level, both reported to fire panel. Tested elevator recall on east elevator, both for 2nd floor as well as basment level, elevator recalled to first floor, west elevator still needs tested for recall, elevator was being serviced at time of inspection.