BLD15-01272
| FIRE-Final Inspection | 6/29/2015 | 6/30/2015 | 6/30/2015 2:40:45 PM | P | PASS |
|
|
Life fir safety passed/complete
|
FIR15-00156
| INSP-Alarm Testing | 6/29/2015 | 6/30/2015 | 6/30/2015 2:27:41 PM | P | PASS |
|
|
Fire alarm inspection passed/complete
|
BLD15-01075
| FIRE-Final Inspection | 6/30/2015 | 6/30/2015 | 6/30/2015 12:50:33 PM | P | FAIL |
|
|
Both exterior entry doors have thumb-turn deadbolt type lock assemblies, deadbolts need to be changed to single action locking hardware. One restroom, located in corridor attached to tenant space (Included in tenant scope of work) has thumb-turn deadbolt type lock assembly, deadbolt needs to be changed to single action locking hardware. No fire extinguisher in tenat space, instructed point of contact that fire extinguisher needs to be installed in tenatnt common area.
|
BLD15-01576
| FIRE-Final Inspection | 6/29/2015 | 6/30/2015 | 6/30/2015 9:25:44 AM | A | CANC |
|
|
No inspection required.
|
BLD14-03175
| FIRE-Final Inspection | 6/29/2015 | 6/30/2015 | 6/30/2015 9:10:18 AM | P | CANC |
|
|
Inspection canceled per conversation with John Phone #: ###-####, superintendent of job, items on job need to be corrected/repaired before inspection can be performed.
|
FIR15-00185
| INSP-Alarm Testing | 6/29/2015 | 6/30/2015 | 6/30/2015 8:32:08 AM | A | PART |
|
|
Inspected/tested horns and strobes, 2nd floor and basement levels, both passed inspection. Activated newly installed pull station 2nd floor and basement level, both reported to fire panel. Tested elevator recall on east elevator, both for 2nd floor as well as basment level, elevator recalled to first floor, west elevator still needs tested for recall, elevator was being serviced at time of inspection.
|