FIR17-00246
| INSP-Final Inspection | 6/30/2017 | 6/30/2017 | 6/30/2017 3:46:38 PM | P | PASS |
|
|
permit finaled
|
FIR17-00114
| INSP-Final Inspection | 6/29/2017 | 6/30/2017 | 6/30/2017 3:46:23 PM | P | PART |
|
|
Temp c of o, phase 3 fire alarm is complete. Fire alarm plans need to be resubmitted for a plan mod due to changes
|
BLD16-04536
| FIRE-Final Inspection | 6/29/2017 | 6/30/2017 | 6/30/2017 3:45:32 PM | P | PART |
|
|
Temp c of o, phase 3 T.I. is ok for life safety. Fire alarm plans need to be resubmitted for a plan mod due to changes
|
BLD17-01315
| FIRE-Final Inspection | 6/29/2017 | 6/30/2017 | 6/30/2017 11:02:34 AM | A | PASS |
|
|
Life safety passed
|
NAF16-00045
| INSP-Final | 6/29/2017 | 6/30/2017 | 6/30/2017 11:02:03 AM | A | PASS |
|
|
Final inspection passed.
|
NAF17-00002
| INSP-Final | 6/29/2017 | 6/30/2017 | 6/30/2017 10:50:01 AM | A | FAIL |
|
|
Plan modifications are required for the changes in the candellas of the wall mounted strobes in the Residence Rooms. I verified the fire sprinkler interconnections with the existing fire alarm panel but stopped the inspection after finding multiple wall mount strobes overspaced in the Resident Rooms. I have not tested horns, strobes, smoke detectors, door release or hvac shutdown.
|
NAF16-00084
| INSP-Final | 6/29/2017 | 6/30/2017 | 6/30/2017 12:00:00 AM | A | DONE |
|
|
Call prior to going Phone #: 9957215 >> Inspection requested via mobile web by Lonnie
|