Inspections for the day of: Wednesday, June 4, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01013 ELE-Aging Inspection6/4/20036/4/20036/4/2003 12:00:00 AM PART
WSUC 6/5/2003 3:29:08 PM
ELE03-01602 Conference6/2/20036/4/20036/4/2003 12:00:00 AMAPART
###-#### 01 with owner basement 6/4/2003 10:32:11 AM
ELE03-01589 Permanent Service6/3/20036/4/20036/4/2003 12:00:00 AMAPASS
service upgrade 200 amp; Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h rec. ok 6/4/2003 9:07:37 AM
ELE03-01173 Final6/3/20036/4/20036/4/2003 12:00:00 AMAPASS
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 6/4/2003 9:45:27 AM
ELE03-01619 Temporary Service6/3/20036/4/20036/4/2003 12:00:00 AMAFAIL
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore needs inuse covers called 6/4/2003 10:58:29 AM
ELE03-01624 Rough-In Permanent Service6/4/20036/4/20036/4/2003 12:00:00 AMPFAIL
###-#### JERRY cor. posted called 300.4(D),250.122 needs #12 equip grd disposal switch, 210.52(B) remove office from kit. circuit, 210.52 (A) add 2 receptacle outlets in kit. for wall space 6/4/2003 3:11:10 PM
ELE02-03818 Final6/4/20036/4/20036/4/2003 12:00:00 AMPPART
###-#### jim temp ok for all araes except banquet room 6/4/2003 4:27:06 PM
ELE02-02684 Conference6/4/20036/4/20036/4/2003 12:00:00 AMPPART
ernest; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 01 ok sprinkler pipes in cable tray not allow 300.8 6/4/2003 1:59:14 PM
ELE03-01564 Electrical Rough-In6/4/20036/4/20036/4/2003 12:00:00 AMPDONE
###-#### stopped at job and called was 06-02-03 by 404 6/4/2003 4:52:56 PM
ELE03-01619 Temporary Service6/4/20036/4/20036/4/2003 12:00:00 AMPPASS
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
t/s u/g new ok 6/4/2003 3:11:47 PM