Inspections for the day of: Monday, June 4, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02413 ELE-Aging Inspection6/4/20076/4/20076/12/2007 2:28:52 PM CANC
ELE07-01769 Final6/4/20076/4/20076/4/2007 2:20:46 PMPPASS
sean; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
ELE07-01807 Electrical Rough-In6/4/20076/4/20076/4/2007 1:45:34 PMPPART
Damon; Phone #: ###-#### Internet Inspection Request from: Darla Downs
new restrm walls and ceiling
ELE07-01989 Final6/4/20076/4/20076/4/2007 1:10:19 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Todd Sellman not ready see added p/s
ELE07-01989 Permanent Service6/4/20076/4/20076/4/2007 1:09:31 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Todd Sellman p/s o/h rec. ok
ELE06-00711 Electrical Rough-In6/1/20076/4/20076/4/2007 12:49:27 PMAPART
Scheduled by a contractor via Hello! on 6/1/2007 at 3:16:23 PM. Contact: ###-####. 2nd floor N tower rms27403, 27308, 20301 walls anop
ELE07-01509 Electrical Rough-In6/4/20076/4/20076/4/2007 12:07:29 PMPNR
greg - equal potential plane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called complete Egrid N & W ends, bond pool cover rails
ELE07-01964 Electrical Rough-In6/1/20076/4/20076/4/2007 10:44:59 AMAPART
john - cover ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
u/g ok jbox island and sub. pumps
ELE06-04493 Final6/1/20076/4/20076/4/2007 10:09:45 AMAFAIL
Scheduled by a contractor via Hello! on 6/1/2007 at 4:25:51 PM. Contact: ###-####. corr called 110.26(F)(2) shall remove curb from in front of p/s for required clearence
ELE07-01718 Electrical Rough-In6/4/20076/4/20076/4/2007 9:48:15 AMAPART
Scheduled by a contractor via Hello! on 6/4/2007 at 7:24:18 AM. needs p/s not r/i , p/s not ready needs meyers hub listed for grding and bonding
ELE06-03281 Electrical Rough-In6/1/20076/4/20076/4/2007 9:21:41 AMAPART
Please inspect 3rd floor B-wing rough-in. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok anop, also looked at genset needs bond bushings
ELE07-01340 Final6/1/20076/4/20076/4/2007 8:05:04 AMAPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok card signed