ELE08-00778
| ELE-Aging Inspection | 6/4/2008 | 6/4/2008 | 6/4/2008 4:19:49 PM | | PART |
|
|
wsuc
|
ELE08-01489
| Electrical Rough-In | 6/3/2008 | 6/4/2008 | 6/4/2008 4:19:19 PM | P | FAIL |
|
|
Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr outlet spacing din rm remove gange hood from SABC remove romex from 1" pvc bottom of p/s needs switch and outside light for back door and clearence for panel no ESC
|
ELE08-01450
| Rough-In Permanent Service | 6/4/2008 | 6/4/2008 | 6/4/2008 3:29:54 PM | P | FAIL |
|
|
Wayne Phone #: ###-#### corr fee due shall not use butt grd on pole needs 2 grd rods for p/s called left message
|
ESC07-01526
| Random Inspection | 6/4/2008 | 6/4/2008 | 6/4/2008 2:35:19 PM | P | PART |
|
|
site ok
|
ELE07-04104
| Final | 6/3/2008 | 6/4/2008 | 6/4/2008 2:34:36 PM | P | PASS |
|
|
Jay Phone #: ###-#### ok
|
ELE08-01443
| Permanent Service | 6/4/2008 | 6/4/2008 | 6/4/2008 1:46:42 PM | P | FAIL |
|
|
john - ###-#### Phone #: ###-#### met owner corr. 250.64 & 92 shall provide required bonding for GEC, 300.10 if rigid used shall provide requied locknuts, 110.26(F)(1) clearence for panel. 408.41 1 neutral per terminal, 250.56 2 grd rods, COW no ESC
|
ELE08-01143
| Electrical Rough-In | 6/4/2008 | 6/4/2008 | 6/4/2008 12:53:16 PM | P | PASS |
|
|
See Lori in suite #202, her # is ###-#### Phone #: ###-#### Internet Inspection Request from: gary batten circuit ok all other under state elevator inspection
|
ELE08-01143
| Final | 6/4/2008 | 6/4/2008 | 6/4/2008 12:52:19 PM | P | PASS |
|
|
See Lori in suite #202, her # is ###-#### Phone #: ###-#### Internet Inspection Request from: gary batten
|
ESC08-00157
| Random Inspection | 6/4/2008 | 6/4/2008 | 6/4/2008 11:29:44 AM | A | PART |
|
|
site ok
|
ELE08-01017
| Final | 6/3/2008 | 6/4/2008 | 6/4/2008 11:29:00 AM | A | PASS |
|
|
George Phone #: ###-#### ok
|
ELE08-01227
| Final | 6/3/2008 | 6/4/2008 | 6/4/2008 11:28:43 AM | A | PASS |
|
|
steve Phone #: ok no ESC
|
ELE08-01494
| Electrical Rough-In | 6/3/2008 | 6/4/2008 | 6/4/2008 10:30:52 AM | A | PART |
|
|
SWIMMING POOL BONDING INSPECTION Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe only pool bond inspected ok no ESC attached
|
ELE08-01419
| Permanent Service | 6/4/2008 | 6/4/2008 | 6/4/2008 10:24:37 AM | P | PART |
|
|
Wayne Phone #: ###-#### conference with contr and ID power inspection ok for work done
|
ESC08-00261
| Site Preparation | 6/4/2008 | 6/4/2008 | 6/4/2008 10:16:53 AM | A | FAIL |
|
|
called contr will correct I will check back 06-05-08, needs card posted bmps in place and clean dirt from gutter
|
ELE08-01181
| Permanent Service | 6/3/2008 | 6/4/2008 | 6/4/2008 10:08:11 AM | A | PASS |
|
|
Mike Phone #: ###-#### needs to install bond strap p/s u/g rec. for meter ok
|
ESC08-00267
| Random Inspection | 6/4/2008 | 6/4/2008 | 6/4/2008 9:52:09 AM | A | CANC |
|
|
|
ELE08-01441
| Permanent Service | 6/3/2008 | 6/4/2008 | 6/4/2008 9:18:43 AM | A | PASS |
|
|
Don Phone #: ###-#### no ESC p/s o/h rec. ok
|
ESC08-00285
| Random Inspection | 6/4/2008 | 6/4/2008 | 6/4/2008 8:41:20 AM | A | PART |
|
|
site ok trash cleaned up
|
ELE08-01458
| Rough-In Permanent Service | 6/3/2008 | 6/4/2008 | 6/4/2008 8:40:27 AM | A | PASS |
|
|
bill Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i p/s u/g new ok
|
ELE07-02781
| Final | 6/3/2008 | 6/4/2008 | 6/4/2008 8:04:08 AM | A | PASS |
|
|
Mike Phone #: ###-#### ok no ESC
|
ELE08-01494
| Electrical Rough-In | 6/3/2008 | 6/4/2008 | 6/3/2008 3:01:11 PM | A | CANC |
|
|
swimming pool bonding inspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe Inspection cancelled from web by: Rowdy Monroe
|