Inspections for the day of: Wednesday, June 4, 2008.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00778 ELE-Aging Inspection6/4/20086/4/20086/4/2008 4:19:49 PM PART
wsuc
ELE08-01489 Electrical Rough-In6/3/20086/4/20086/4/2008 4:19:19 PMPFAIL
Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr outlet spacing din rm remove gange hood from SABC remove romex from 1" pvc bottom of p/s needs switch and outside light for back door and clearence for panel no ESC
ELE08-01450 Rough-In Permanent Service6/4/20086/4/20086/4/2008 3:29:54 PMPFAIL
Wayne Phone #: ###-#### corr fee due
shall not use butt grd on pole needs 2 grd rods for p/s called left message
ESC07-01526 Random Inspection6/4/20086/4/20086/4/2008 2:35:19 PMPPART
site ok
ELE07-04104 Final6/3/20086/4/20086/4/2008 2:34:36 PMPPASS
Jay Phone #: ###-#### ok
ELE08-01443 Permanent Service6/4/20086/4/20086/4/2008 1:46:42 PMPFAIL
john - ###-#### Phone #: ###-#### met owner corr. 250.64 & 92 shall provide required bonding for GEC, 300.10 if rigid used shall provide requied locknuts, 110.26(F)(1) clearence for panel. 408.41 1 neutral per terminal, 250.56 2 grd rods, COW no ESC
ELE08-01143 Electrical Rough-In6/4/20086/4/20086/4/2008 12:53:16 PMPPASS
See Lori in suite #202, her # is ###-#### Phone #: ###-#### Internet Inspection Request from: gary batten circuit ok all other under state elevator inspection
ELE08-01143 Final6/4/20086/4/20086/4/2008 12:52:19 PMPPASS
See Lori in suite #202, her # is ###-#### Phone #: ###-#### Internet Inspection Request from: gary batten
ESC08-00157 Random Inspection6/4/20086/4/20086/4/2008 11:29:44 AMAPART
site ok
ELE08-01017 Final6/3/20086/4/20086/4/2008 11:29:00 AMAPASS
George Phone #: ###-#### ok
ELE08-01227 Final6/3/20086/4/20086/4/2008 11:28:43 AMAPASS
steve Phone #: ok no ESC
ELE08-01494 Electrical Rough-In6/3/20086/4/20086/4/2008 10:30:52 AMAPART
SWIMMING POOL BONDING INSPECTION Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe
only pool bond inspected ok no ESC
attached
ELE08-01419 Permanent Service6/4/20086/4/20086/4/2008 10:24:37 AMPPART
Wayne Phone #: ###-#### conference with contr and ID power inspection ok for work done
ESC08-00261 Site Preparation6/4/20086/4/20086/4/2008 10:16:53 AMAFAIL
called contr will correct I will check back 06-05-08, needs card posted bmps in place and clean dirt from gutter
ELE08-01181 Permanent Service6/3/20086/4/20086/4/2008 10:08:11 AMAPASS
Mike Phone #: ###-#### needs to install bond strap p/s u/g rec. for meter ok
ESC08-00267 Random Inspection6/4/20086/4/20086/4/2008 9:52:09 AMACANC
ELE08-01441 Permanent Service6/3/20086/4/20086/4/2008 9:18:43 AMAPASS
Don Phone #: ###-#### no ESC
p/s o/h rec. ok
ESC08-00285 Random Inspection6/4/20086/4/20086/4/2008 8:41:20 AMAPART
site ok trash cleaned up
ELE08-01458 Rough-In Permanent Service6/3/20086/4/20086/4/2008 8:40:27 AMAPASS
bill Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i p/s u/g new ok
ELE07-02781 Final6/3/20086/4/20086/4/2008 8:04:08 AMAPASS
Mike Phone #: ###-#### ok no ESC
ELE08-01494 Electrical Rough-In6/3/20086/4/20086/3/2008 3:01:11 PMACANC
swimming pool bonding inspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe Inspection cancelled from web by: Rowdy Monroe