Inspections for the day of: Wednesday, June 4, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00874 INSP-Sprinkler Rough-in/Hydro6/3/20086/4/20086/4/2008 4:44:50 PMPPASS
The dry system hydro test for the Aid Station and the Dining area passed.
FIR07-00999 INSP-Alarm Testing6/3/20086/4/20086/4/2008 3:38:41 PMPFAIL
Provide an additional smoke detector near the main entrance as discussed and relocate the manual pull station to within 5' of the same door. Provide asbuilts showing the deletion of the NAC panel and new battery calculations.
FIR07-00887 INSP-Final Inspection6/3/20086/4/20086/4/2008 3:36:39 PMPPASS
Permit finaled
BLD07-02067 FIRE-Final Inspection6/3/20086/4/20086/4/2008 3:35:43 PMPFAIL
Needs the project related fire alarm and fire sprinkler permits finaled prior to this inspection. Contractor and I discussed the fire dept access requirements.
FIR07-00909 INSP-Final Inspection6/3/20086/4/20086/4/2008 3:33:51 PMPFAIL
The flow switch needs replaced and retested.
BLD08-01079 FIRE-Final Inspection6/4/20086/4/20086/4/2008 3:33:01 PMPPASS
life safety passed
FIR08-00311 INSP-Final Inspection6/3/20086/4/20086/4/2008 3:32:14 PMPFAIL
The duct smoke detectors have been mounted incorrectly. The flow switch needs replaced and tested again. The zone description for the asbuilts needs corrected.