Inspections for the day of: Thursday, June 4, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC08-00637 General Inspection6/4/20096/4/20096/4/2009 4:07:47 PMPPASS
looked ok, still working on site
ELE08-03179 Final6/4/20096/4/20096/4/2009 4:06:54 PMPPASS
Scheduled by a contractor via Hello! on 6/4/2009 at 9:26:47 AM. Contact: ###-####. house looked at earlier, u/g ok to cover, looked at garage, ok to final
ELE09-00738 Final6/4/20096/4/20096/4/2009 4:00:47 PMPPASS
Enter thru gate on east side of home. Bathroom has exterior entrance on lower level. Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final, no esc this project
ELE09-00537 Final6/3/20096/4/20096/4/2009 3:32:59 PMPPASS
Call Jimmy @ ###-#### for Questions. Job is at the big mike exhibit kiosk at the train depot. Phone #: ###-#### Internet Inspection Request from: John Edwards ok to final, no esc this project
ESC08-00660 General Inspection6/4/20096/4/20096/4/2009 2:58:47 PMPPASS
looked ok
ELE09-00964 Final6/4/20096/4/20096/4/2009 2:16:35 PMPPASS
Keith Phone #: ###-#### ok to final, no esc this project
ELE09-00965 Electrical Rough-In6/4/20096/4/20096/4/2009 1:30:11 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ric ok, no esc this project
ELE09-00864 Permanent Service6/4/20096/4/20096/4/2009 12:28:28 PMPPASS
gene Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE09-00676 Final6/4/20096/4/20096/4/2009 10:35:52 AMPPASS
jared Phone #: ###-#### ok to final, no esc this project
ELE09-00473 Final6/3/20096/4/20096/4/2009 10:15:50 AMAPASS
call jimmy @ ###-#### for Questions. Phone #: ###-#### Internet Inspection Request from: John Edwards called to have covers installed and ground poles, ok to final, no esc this project
ELE09-00964 Permanent Service6/4/20096/4/20096/4/2009 9:55:39 AMPPASS
fred Phone #: ###-#### p/s u/g rec ok, no esc this project, check for tree clearance at service and ground connection at final
ELE09-00873 Final6/3/20096/4/20096/4/2009 9:30:16 AMAFAIL
andy Phone #: ###-#### or 345-669 called, left correction notice, NEC 600.5 shall provide 20A sign outlet, 210.62 shall provide showroom receptacle within 18" of top of show window, 422.31 shall provide water heater disconnect, 110.3(B) listed equipment shall be installed per directions- hot and neutral reversed by rear sink, BCC no violations shall be retained
ELE08-02231 Final6/3/20096/4/20096/4/2009 8:47:35 AMAPASS
Mike-please call prior to inspection--issues regarding electrical contractor didn''t do any rooms just service Phone #: ###-#### ok to final, no esc this project
ELE08-03235 Final6/3/20096/4/20096/4/2009 8:02:26 AMAPASS
jared Phone #: ###-#### ok to final, no esc this project