Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00794 FIRE-Final Inspection6/4/20096/4/20096/5/2009 9:15:36 AMPCANC
To be rescheduled for tomorrow
FIR08-00603 INSP-Final Inspection6/3/20096/4/20096/5/2009 9:15:06 AMAFAIL
No inspection was performed. The monitoring had not been set up completely, manual pull stations are mounted too high, door holders had not been completely installed and wired into the fire alarm panel, an hvac control wire was not connected to the panel yet and an electrical/fire alarm box behind the wet sprinkler riser did not have a cover installed. These are just items noted initially and is not a complete list of possible corrections needed.
BLD09-00568 FIRE-Final Inspection6/4/20096/4/20096/4/2009 3:33:16 PMPPASS
Life safety passed
BLD09-00623 FIRE-Final Inspection6/3/20096/4/20096/4/2009 3:31:50 PMAPASS
Life safety passed
FIR09-00113 FIR-Aging Inspection6/4/20096/4/20096/4/2009 10:39:05 AM NR
work is in progress
BLD09-00794 FIRE-Final Inspection6/3/20096/4/20096/4/2009 10:31:32 AMAPART
A temporary occupancy was given until the thumbturn lock and round knob on the front door is removed as discussed. Also the fire extinguisher needs tagged and an additional one provided upstairs.