Inspections for the day of: Friday, June 4, 2010.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01244 ELE-Aging Inspection6/4/20106/4/20106/8/2010 7:23:33 AM DONE
suc
ELE10-01124 Rough-In Permanent Service6/4/20106/4/20106/7/2010 9:25:28 AMPFAIL
Please call me 30 minutes prior to arrival so i can arrange entry. Inspection requested from web by: John Edwards Phone #: ###-#### met contractor, left correction notice, NEC 110.26 dedicated space shall be provided, 300.4 shall provide nailplates, 210.52(A)(1) shall provide outlet spacing in new walls Note: corrections sahll be made in 5 working days or further action will be taken
ELE10-00236 Final6/4/20106/4/20106/7/2010 8:19:32 AMPPASS
Rocky-If you can''t make the inspection prior to 3pm today then please reschedule for Mon am as they close at 3 today-thanks Phone #: ###-#### ok to final, signed card
ELE09-00104 Final6/4/20106/4/20106/7/2010 7:48:02 AMPPASS
ty Phone #: ###-#### ok to final
ELE10-01227 Conference6/3/20106/4/20106/4/2010 3:47:40 PMPDONE
requests after 3pm//Jeremiah ###-#### talked about re- wiring old house up to current code
ELE09-02046 Electrical Rough-In6/4/20106/4/20106/4/2010 3:40:56 PMPPASS
Someone will be there. Inspection requested from web by: Clay Morgan Phone #: ###-#### called, left message, ric ok
ELE10-00667 Final6/3/20106/4/20106/4/2010 3:04:16 PMPPART
Inspection requested from web by: Clint Tate Phone #: ###-#### need to see cash wrap when done, signed card, check for 400.5 feeding cash wrap
ELE10-01218 Final6/4/20106/4/20106/4/2010 2:14:47 PMPCANC
Final service inspection request. Contact is Dave Bradshaw ###-####. Inspection requested from web by: Scott Campbell Phone #: ###-#### wrong type request, see p/s
ELE10-01218 Permanent Service6/4/20106/4/20106/4/2010 1:47:21 PMPPASS
Final service inspection request. Contact is Dave Bradshaw ###-####. Inspection requested from web by: Scott Campbell Phone #: ###-#### called, p/s u/g n ok
ELE10-01131 Final6/3/20106/4/20106/4/2010 1:46:12 PMPPASS
Jerry Phone #: ###-#### ok to final, signed card
ELE10-01219 Final6/4/20106/4/20106/4/2010 1:13:29 PMPCANC
Final service inspection request. Contact Dave Bradshaw ###-#### Inspection requested from web by: Scott Campbell Phone #: ###-#### wrong type request, see p/s
ELE10-01219 Permanent Service6/4/20106/4/20106/4/2010 1:08:03 PMPPASS
Final service inspection request. Contact Dave Bradshaw ###-#### Inspection requested from web by: Scott Campbell Phone #: ###-#### p/s u/g rec ok
ELE10-01210 Electrical Rough-In6/4/20106/4/20106/4/2010 1:06:51 PMPPASS
kevin Phone #: ###-#### corrections made ric ok
ELE09-01409 Final6/3/20106/4/20106/4/2010 12:16:21 PMAPART
this inspection is for the 2nd floor at the Lowell elementary school project. Contact Jeff if there are any questions ###-#### Inspection requested from web by: Spencer Mclean Phone #: ###-#### left correction notice, NEC 210.8(B)(5) shall provide gfci receptacles within 6' of sink, BCC 4-05033 A,B all equipment shall be listed by a nationally recognized testing laboratory, Note: corrections shall be made within 5 working days or further action will be taken
ELE10-01203 Electrical Rough-In6/4/20106/4/20106/4/2010 11:30:42 AMPPASS
Please contact Steve Harris Inspection requested from web by: Kevin Perez Phone #: ###-#### walls only ok to cover
ELE10-01177 Electrical Rough-In6/3/20106/4/20106/4/2010 11:25:58 AMAPASS
Please contact Steve Harris on jobsite Inspection requested from web by: Kevin Perez Phone #: ###-#### walls only ok to cover
ELE10-01224 Rough-In Permanent Service6/3/20106/4/20106/4/2010 10:50:16 AMAFAIL
THANKS, BILL Inspection requested from web by: Bob Glenn Phone #: ###-#### called, left correction notice, NEC 334.23 nm cable installed in accessible attics shall comply with 320.23, 210.52(A)(1) one receptacle shall be installed at back of dwelling, Note: corrections shall be made in 5 working days or further action will be taken
ELE10-01222 Electrical Rough-In6/3/20106/4/20106/4/2010 9:37:43 AMAPART
jason Phone #: ###-#### walls only anop
ELE10-00120 Final6/3/20106/4/20106/4/2010 9:32:41 AMAPASS
Please call 30 minutes prior to inspection. Thank you. John ###-#### Inspection requested from web by: John VanZandt Phone #: ###-#### called, ok to final
ELE08-01186 ELE-Aging Inspection6/4/20106/4/20106/4/2010 7:23:37 AM DONE
suc
ELE06-04611 ELE-Aging Inspection6/4/20106/4/20106/4/2010 7:22:12 AM DONE
see doc expire
ELE06-04611 DOC - Permit Expired6/4/20106/4/20106/4/2010 7:22:02 AMAPASS
no activity
ELE06-04612 ELE-Aging Inspection6/4/20106/4/20106/4/2010 7:20:52 AM DONE
see doc expire
ELE06-04612 DOC - Permit Expired6/4/20106/4/20106/4/2010 7:20:40 AMAPASS
no activity