ELE08-01244
| ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/8/2010 7:23:33 AM | | DONE |
|
|
suc
|
ELE10-01124
| Rough-In Permanent Service | 6/4/2010 | 6/4/2010 | 6/7/2010 9:25:28 AM | P | FAIL |
|
|
Please call me 30 minutes prior to arrival so i can arrange entry. Inspection requested from web by: John Edwards Phone #: ###-#### met contractor, left correction notice, NEC 110.26 dedicated space shall be provided, 300.4 shall provide nailplates, 210.52(A)(1) shall provide outlet spacing in new walls Note: corrections sahll be made in 5 working days or further action will be taken
|
ELE10-00236
| Final | 6/4/2010 | 6/4/2010 | 6/7/2010 8:19:32 AM | P | PASS |
|
|
Rocky-If you can''t make the inspection prior to 3pm today then please reschedule for Mon am as they close at 3 today-thanks Phone #: ###-#### ok to final, signed card
|
ELE09-00104
| Final | 6/4/2010 | 6/4/2010 | 6/7/2010 7:48:02 AM | P | PASS |
|
|
ty Phone #: ###-#### ok to final
|
ELE10-01227
| Conference | 6/3/2010 | 6/4/2010 | 6/4/2010 3:47:40 PM | P | DONE |
|
|
requests after 3pm//Jeremiah ###-#### talked about re- wiring old house up to current code
|
ELE09-02046
| Electrical Rough-In | 6/4/2010 | 6/4/2010 | 6/4/2010 3:40:56 PM | P | PASS |
|
|
Someone will be there. Inspection requested from web by: Clay Morgan Phone #: ###-#### called, left message, ric ok
|
ELE10-00667
| Final | 6/3/2010 | 6/4/2010 | 6/4/2010 3:04:16 PM | P | PART |
|
|
Inspection requested from web by: Clint Tate Phone #: ###-#### need to see cash wrap when done, signed card, check for 400.5 feeding cash wrap
|
ELE10-01218
| Final | 6/4/2010 | 6/4/2010 | 6/4/2010 2:14:47 PM | P | CANC |
|
|
Final service inspection request. Contact is Dave Bradshaw ###-####. Inspection requested from web by: Scott Campbell Phone #: ###-#### wrong type request, see p/s
|
ELE10-01218
| Permanent Service | 6/4/2010 | 6/4/2010 | 6/4/2010 1:47:21 PM | P | PASS |
|
|
Final service inspection request. Contact is Dave Bradshaw ###-####. Inspection requested from web by: Scott Campbell Phone #: ###-#### called, p/s u/g n ok
|
ELE10-01131
| Final | 6/3/2010 | 6/4/2010 | 6/4/2010 1:46:12 PM | P | PASS |
|
|
Jerry Phone #: ###-#### ok to final, signed card
|
ELE10-01219
| Final | 6/4/2010 | 6/4/2010 | 6/4/2010 1:13:29 PM | P | CANC |
|
|
Final service inspection request. Contact Dave Bradshaw ###-#### Inspection requested from web by: Scott Campbell Phone #: ###-#### wrong type request, see p/s
|
ELE10-01219
| Permanent Service | 6/4/2010 | 6/4/2010 | 6/4/2010 1:08:03 PM | P | PASS |
|
|
Final service inspection request. Contact Dave Bradshaw ###-#### Inspection requested from web by: Scott Campbell Phone #: ###-#### p/s u/g rec ok
|
ELE10-01210
| Electrical Rough-In | 6/4/2010 | 6/4/2010 | 6/4/2010 1:06:51 PM | P | PASS |
|
|
kevin Phone #: ###-#### corrections made ric ok
|
ELE09-01409
| Final | 6/3/2010 | 6/4/2010 | 6/4/2010 12:16:21 PM | A | PART |
|
|
this inspection is for the 2nd floor at the Lowell elementary school project. Contact Jeff if there are any questions ###-#### Inspection requested from web by: Spencer Mclean Phone #: ###-#### left correction notice, NEC 210.8(B)(5) shall provide gfci receptacles within 6' of sink, BCC 4-05033 A,B all equipment shall be listed by a nationally recognized testing laboratory, Note: corrections shall be made within 5 working days or further action will be taken
|
ELE10-01203
| Electrical Rough-In | 6/4/2010 | 6/4/2010 | 6/4/2010 11:30:42 AM | P | PASS |
|
|
Please contact Steve Harris Inspection requested from web by: Kevin Perez Phone #: ###-#### walls only ok to cover
|
ELE10-01177
| Electrical Rough-In | 6/3/2010 | 6/4/2010 | 6/4/2010 11:25:58 AM | A | PASS |
|
|
Please contact Steve Harris on jobsite Inspection requested from web by: Kevin Perez Phone #: ###-#### walls only ok to cover
|
ELE10-01224
| Rough-In Permanent Service | 6/3/2010 | 6/4/2010 | 6/4/2010 10:50:16 AM | A | FAIL |
|
|
THANKS, BILL Inspection requested from web by: Bob Glenn Phone #: ###-#### called, left correction notice, NEC 334.23 nm cable installed in accessible attics shall comply with 320.23, 210.52(A)(1) one receptacle shall be installed at back of dwelling, Note: corrections shall be made in 5 working days or further action will be taken
|
ELE10-01222
| Electrical Rough-In | 6/3/2010 | 6/4/2010 | 6/4/2010 9:37:43 AM | A | PART |
|
|
jason Phone #: ###-#### walls only anop
|
ELE10-00120
| Final | 6/3/2010 | 6/4/2010 | 6/4/2010 9:32:41 AM | A | PASS |
|
|
Please call 30 minutes prior to inspection. Thank you. John ###-#### Inspection requested from web by: John VanZandt Phone #: ###-#### called, ok to final
|
ELE08-01186
| ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/4/2010 7:23:37 AM | | DONE |
|
|
suc
|
ELE06-04611
| ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/4/2010 7:22:12 AM | | DONE |
|
|
see doc expire
|
ELE06-04611
| DOC - Permit Expired | 6/4/2010 | 6/4/2010 | 6/4/2010 7:22:02 AM | A | PASS |
|
|
no activity
|
ELE06-04612
| ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/4/2010 7:20:52 AM | | DONE |
|
|
see doc expire
|
ELE06-04612
| DOC - Permit Expired | 6/4/2010 | 6/4/2010 | 6/4/2010 7:20:40 AM | A | PASS |
|
|
no activity
|