Inspections for the day of: Tuesday, June 4, 2013.
Number of inspections: 9
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02367 FIRE-Final Inspection5/29/20135/30/2013 A 
Contact on site, or Dave at ###-####
FIR12-00108 INSP-Sprinkler Rough-in6/3/20136/4/20136/6/2013 10:40:21 PMPPASS
Need a RTC for the basement. Please call Trent 30 mins prior at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
FIR13-00242 INSP-Final Inspection6/3/20136/4/20136/5/2013 1:12:35 PMPFAIL
Manual pull needs to meet location guidelines per IFC 2009 sec. 904.11.1, provide verification the fire alarm panel is monitoring hood suppression activation. Makeup air does not appear functional. Link test completed okay.
BLD13-00807 FIRE-Final Inspection6/4/20136/4/20136/5/2013 9:31:51 AMPPASS
Fire life safety inspection passed.
BLD12-01734 FIRE-Final Inspection6/3/20136/4/20136/4/2013 12:58:53 PMAPART
"Phase two" partial fire life safety inspection completed. Provide ceiling tile at the soiled utility room.
BLD12-03321 FIRE-Final Inspection6/3/20136/4/20136/4/2013 11:54:28 AMPPASS
Fire life safety inspection completed satisfactory. Noted correction items finished.
FIR13-00068 INSP-Final Inspection6/3/20136/4/20136/4/2013 11:52:53 AMPPASS
Remainder of correction items verified for completion, final walkthrough passed. Fire sprinkler permit finaled.
BLD13-01334 FIRE-Final Inspection6/3/20136/4/20136/4/2013 11:40:46 AMAPASS
Noted correction items completed. Life safety finaled.
BLD13-01333 FIRE-Final Inspection6/3/20136/4/20136/4/2013 11:39:37 AMAPASS
C/N items finished, life safety passed.