BLD11-02367
| FIRE-Final Inspection | 5/29/2013 | 5/30/2013 | | A | |
|
|
Contact on site, or Dave at ###-####
|
FIR12-00108
| INSP-Sprinkler Rough-in | 6/3/2013 | 6/4/2013 | 6/6/2013 10:40:21 PM | P | PASS |
|
|
Need a RTC for the basement. Please call Trent 30 mins prior at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
|
FIR13-00242
| INSP-Final Inspection | 6/3/2013 | 6/4/2013 | 6/5/2013 1:12:35 PM | P | FAIL |
|
|
Manual pull needs to meet location guidelines per IFC 2009 sec. 904.11.1, provide verification the fire alarm panel is monitoring hood suppression activation. Makeup air does not appear functional. Link test completed okay.
|
BLD13-00807
| FIRE-Final Inspection | 6/4/2013 | 6/4/2013 | 6/5/2013 9:31:51 AM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD12-01734
| FIRE-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 12:58:53 PM | A | PART |
|
|
"Phase two" partial fire life safety inspection completed. Provide ceiling tile at the soiled utility room.
|
BLD12-03321
| FIRE-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 11:54:28 AM | P | PASS |
|
|
Fire life safety inspection completed satisfactory. Noted correction items finished.
|
FIR13-00068
| INSP-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 11:52:53 AM | P | PASS |
|
|
Remainder of correction items verified for completion, final walkthrough passed. Fire sprinkler permit finaled.
|
BLD13-01334
| FIRE-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 11:40:46 AM | A | PASS |
|
|
Noted correction items completed. Life safety finaled.
|
BLD13-01333
| FIRE-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 11:39:37 AM | A | PASS |
|
|
C/N items finished, life safety passed.
|