FIR09-00051
| FIR-Aging Inspection | 6/4/2014 | 6/4/2014 | 6/10/2014 8:14:24 AM | | NR |
|
|
Original contractor is out of business. Waiting for Taylor brothers to call in inspection.
|
FIR14-00278
| INSP-Final Inspection | 6/4/2014 | 6/4/2014 | 6/4/2014 3:17:59 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00129
| INSP-Final Inspection | 6/4/2014 | 6/4/2014 | 6/4/2014 2:52:20 PM | P | FAIL |
|
|
All devices tested ok but a 117cd strobe needs to be added in the ADA room or the 110cd strobe needs to be lowered to less than 24"
|
BLD14-00402
| FIRE-Final Inspection | 6/3/2014 | 6/4/2014 | 6/4/2014 2:51:07 PM | A | FAIL |
|
|
Need to provide all of the small documents. Exit signs and emergency lights are not installed and neither is the south exit door. Need fire extinguishers as well with current inspection tags.
|
FIR13-00557
| INSP-Sprinkler Rough-in | 6/3/2014 | 6/4/2014 | 6/4/2014 1:05:06 PM | A | PASS |
|
|
24 hour air test started at 7:30 with 42psi on the guage. Piping in the racks and the freezer area passed. Branchline restraints are required to be installed in the freezer area.
|
BLD14-01042
| FIRE-Final Inspection | 6/3/2014 | 6/4/2014 | 6/4/2014 9:55:13 AM | A | PASS |
|
|
life safety passed
|
BLD13-03265
| FIRE-Final Inspection | 6/3/2014 | 6/4/2014 | 6/4/2014 9:45:49 AM | A | PASS |
|
|
life safety passed
|
BLD14-01471
| FIRE-Final Inspection | 6/3/2014 | 6/4/2014 | 6/4/2014 12:00:00 AM | A | CANC |
|
|