MIS18-00214
| ELE-Conference | 6/4/2018 | 6/4/2018 | 6/4/2018 3:08:38 PM | P | FAIL |
|
|
Call Jack Reynolds before you go out Phone #: ###-#### 210.63- A receptacle outlet shall be installed with in 25" of an HVAC unit. Roof east end. 300.15- All unused cables shall terminate in a box. Cable above bathroom ceilings shall be in a box. Disconnect unused wiring from over current devices. 440.6- Ampacities shall not exceed that posted on nameplate. Roof top minisplit units have max ampacity of 15 amp with 20 amp installed. Electrical contractor must pull permit and complete corrections. Will check back in 7 days for permit.
|
ELE18-02011
| Electrical Rough-In | 6/1/2018 | 6/4/2018 | 6/4/2018 2:26:32 PM | P | PASS |
|
|
Please call prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor Cubical and break area walls only rough in ok cover
|
ELE18-01425
| Final | 6/1/2018 | 6/4/2018 | 6/4/2018 1:04:36 PM | A | PASS |
|
|
Russ McCrea Phone #: ###-#### Inspection requested via web by Judy Spencer Final ok
|
ELE18-01425
| Electrical Rough-In | 6/4/2018 | 6/4/2018 | 6/4/2018 12:30:07 PM | P | PASS |
|
|
Russ McCrea Phone #: ###-#### Inspection requested via web by Judy Spencer Some receptacles surface conduits and rest fished in. Rough in ok
|
ELE18-01962
| Final | 6/1/2018 | 6/4/2018 | 6/4/2018 12:16:10 PM | A | PASS |
|
|
Recessed can blank covers are on back order. Will install as soon as they are received. Phone #: ###-#### Inspection requested via web by Cortney Hopper Final ok
|
ELE18-01962
| Electrical Rough-In | 6/4/2018 | 6/4/2018 | 6/4/2018 12:16:01 PM | P | PASS |
|
|
Recessed can blank covers are on back order. Will install as soon as they are received. Phone #: ###-#### Inspection requested via web by Cortney Hopper All wiring existing surface conduits. Rough in ok
|
ELE17-01337
| Electrical Rough-In | 6/1/2018 | 6/4/2018 | 6/4/2018 11:35:26 AM | A | PEND |
|
|
We are requesting a drop ceiling inspection for floors 2, 3, 4, and 5 for Monday morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Levels 2 thru 5 corridor grid rough in ok cover
|
MIS18-00206
| ELE-Final | 6/4/2018 | 6/4/2018 | 6/4/2018 10:40:35 AM | P | PASS |
|
|
electrical and plumbing permits pulled. Final ok
|
ELE18-02064
| Electrical Rough-In | 6/1/2018 | 6/4/2018 | 6/4/2018 10:38:49 AM | A | PART |
|
|
Rough-in for master bed area Phone #: ###-#### Inspection requested via web by Kevin Perez Homeowner had 1st general contactor skip town now has another to complete work. Some patch work in upstair ceiling only ok
|
ELE17-02095
| Final | 6/4/2018 | 6/4/2018 | 6/4/2018 9:58:33 AM | P | PASS |
|
|
please note the final for the other permit at this site is a mistake and not ready yet. Mike Cole Phone #: ###-#### Inspection requested via web by Mike Cole Apartment only final ok
|
ELE18-01937
| Final | 6/1/2018 | 6/4/2018 | 6/4/2018 9:57:58 AM | A | NR |
|
|
Mike Phone #: ###-#### Contact informed me this requested by mistake. Will recall when ready.
|
ELE17-03778
| Conference | 6/4/2018 | 6/4/2018 | 6/4/2018 9:44:53 AM | P | DONE |
|
|
Discussed which code cycle being enforced of this job. Plan were submitted for review 6-5-17 which is prior to the adoption of 2017 NEC. 2014 NEC code apply.
|
ELE18-02073
| Electrical Rough-In | 6/1/2018 | 6/4/2018 | 6/4/2018 9:18:31 AM | A | PASS |
|
|
bathrooms only// should be someone there to let you in, but if not call him to get code // Alan Phone #: ###-#### Bathrooms only rough in ok cover
|
ELE18-02054
| Rough-In Permanent Service | 6/1/2018 | 6/4/2018 | 6/4/2018 9:04:47 AM | A | NH |
|
|
key on top of back door jamp Phone #: ###-#### Inspection requested via web by Paula Gratiot Unable to locate key will recall when accessible.
|