Inspections for the day of: Monday, June 4, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS18-00214 ELE-Conference6/4/20186/4/20186/4/2018 3:08:38 PMPFAIL
Call Jack Reynolds before you go out Phone #: ###-####
210.63- A receptacle outlet shall be installed with in 25" of an HVAC unit. Roof east end.
300.15- All unused cables shall terminate in a box. Cable above bathroom ceilings shall be in a box. Disconnect unused wiring from over current devices.
440.6- Ampacities shall not exceed that posted on nameplate. Roof top minisplit units have max ampacity of 15 amp with 20 amp installed.
Electrical contractor must pull permit and complete corrections. Will check back in 7 days for permit.
ELE18-02011 Electrical Rough-In6/1/20186/4/20186/4/2018 2:26:32 PMPPASS
Please call prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor
Cubical and break area walls only rough in ok cover
ELE18-01425 Final6/1/20186/4/20186/4/2018 1:04:36 PMAPASS
Russ McCrea Phone #: ###-#### Inspection requested via web by Judy Spencer Final ok
ELE18-01425 Electrical Rough-In6/4/20186/4/20186/4/2018 12:30:07 PMPPASS
Russ McCrea Phone #: ###-#### Inspection requested via web by Judy Spencer
Some receptacles surface conduits and rest fished in. Rough in ok
ELE18-01962 Final6/1/20186/4/20186/4/2018 12:16:10 PMAPASS
Recessed can blank covers are on back order. Will install as soon as they are received. Phone #: ###-#### Inspection requested via web by Cortney Hopper Final ok
ELE18-01962 Electrical Rough-In6/4/20186/4/20186/4/2018 12:16:01 PMPPASS
Recessed can blank covers are on back order. Will install as soon as they are received. Phone #: ###-#### Inspection requested via web by Cortney Hopper
All wiring existing surface conduits. Rough in ok
ELE17-01337 Electrical Rough-In6/1/20186/4/20186/4/2018 11:35:26 AMAPEND
We are requesting a drop ceiling inspection for floors 2, 3, 4, and 5 for Monday morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Levels 2 thru 5 corridor grid rough in ok cover
MIS18-00206 ELE-Final6/4/20186/4/20186/4/2018 10:40:35 AMPPASS
electrical and plumbing permits pulled. Final ok
ELE18-02064 Electrical Rough-In6/1/20186/4/20186/4/2018 10:38:49 AMAPART
Rough-in for master bed area Phone #: ###-#### Inspection requested via web by Kevin Perez
Homeowner had 1st general contactor skip town now has another to complete work. Some patch work in upstair ceiling only ok
ELE17-02095 Final6/4/20186/4/20186/4/2018 9:58:33 AMPPASS
please note the final for the other permit at this site is a mistake and not ready yet.
Mike Cole Phone #: ###-#### Inspection requested via web by Mike Cole
Apartment only final ok
ELE18-01937 Final6/1/20186/4/20186/4/2018 9:57:58 AMANR
Mike Phone #: ###-#### Contact informed me this requested by mistake. Will recall when ready.
ELE17-03778 Conference6/4/20186/4/20186/4/2018 9:44:53 AMPDONE
Discussed which code cycle being enforced of this job. Plan were submitted for review 6-5-17 which is prior to the adoption of 2017 NEC. 2014 NEC code apply.
ELE18-02073 Electrical Rough-In6/1/20186/4/20186/4/2018 9:18:31 AMAPASS
bathrooms only// should be someone there to let you in, but if not call him to get code // Alan Phone #: ###-####
Bathrooms only rough in ok cover
ELE18-02054 Rough-In Permanent Service6/1/20186/4/20186/4/2018 9:04:47 AMANH
key on top of back door jamp Phone #: ###-#### Inspection requested via web by Paula Gratiot
Unable to locate key will recall when accessible.