Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-06013 Pressure Test6/4/20196/4/20196/4/2019 3:16:10 PMPCANC
DARBY IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER - Unable to do inspection because of paving in progress. rescheduled inspection for tomorrow morning.
MEC18-04797 Rough-in6/3/20196/4/20196/4/2019 11:01:47 AMAPART
R/I Inspection for Room 406 ; Trash Chute. Please call Curt @ ###-#### before coming out. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 406 pass, trash chute duct fail, need to seal back side of ductwork
MEC18-06013 Pressure Test6/3/20196/4/20196/4/2019 10:30:50 AMAFAIL
DARBY IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER - 20lb gas fail on maintance building, gauge stuck, should be a 60lb test. 20lb gas pass for anteater building.
MEC19-01212 Rough-in6/3/20196/4/20196/4/2019 10:01:13 AMAPART
We would like to schedule a partial duct rough-in inspection for St. Luke''s Surgery Center. Jim Brown is the site contact ###-#### please call in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical - Okay to insulate the high pressure duct