Inspections for the day of: Thursday, June 4, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00898 Final6/3/20206/4/20206/4/2020 2:37:03 PMPPASS
John Sutton will be in his office at the end of the hall all afternoon and he will let you into the front area for inspection please call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe No card posted. Final ok
ELE20-01877 Rough-In Permanent Service6/3/20206/4/20206/4/2020 2:05:40 PMAFAIL
Underground conduits for service and new meter pack Phone #: ###-#### Inspection requested via web by Casey Fouts
230.42- Service entrance conductors shall be installed from meter to panel to verify size. 300.5(D)(3)- Service entrance underground conductors18" and deeper shall be marked with warning tape. 300.5(F)- soft backfill shall be installed to protect conduit from large rocks.
Contractor called, sand being delivered, tape planned at required 12" above pipe. Will recall when ready.
ELE20-01851 Permanent Service6/1/20206/4/20206/4/2020 2:03:46 PMPPASS
Jeff is the site contact, would like to request an early afternoon inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Seperate BLD and ELE for garage addition. Request final when circuit directory complete. p/s u/g rec ok
ELE20-01895 Electrical Rough-In6/3/20206/4/20206/4/2020 1:34:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Offices N.W. corner as noted on contractor print wall rough in ok cover
ELE19-04799 Electrical Rough-In6/4/20206/4/20206/4/2020 11:40:17 AMAPASS
Underground at alley and parking equipment island Phone #: ###-#### Inspection requested via web by Jason Parke
Central alley, east parking entrance south island underground rough in ok cover.
ELE19-00601 Electrical Rough-In6/4/20206/4/20206/4/2020 10:33:39 AMAPASS
5th floor vending area cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Room noted walls and hardlid rough in ok cover.
ELE20-01801 Rough-In Permanent Service6/3/20206/4/20206/4/2020 9:26:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard
Rough in ok cover p/s u/g n ok