ELE00-02037
| Electrical Rough-In | 6/2/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 06/02/2000 at 13:15:12. Contact: ###-####. Walls ele. R/I 6/6/00 11:39:41 AM
|
ELE00-02046
| Electrical Rough-In | 6/2/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 06/02/2000 at 14:26:09. Contact: ###-####. Walls Ele. R/I; fast enterprises. 6/6/00 11:39:54 AM
|
ELE00-01881
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/05/2000 at 07:12:52. Contact: ###-####. Corrections completed 6/6/00 11:40:01 AM
|
ELE00-01117
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 06/05/2000 at 07:16:46. Contact: ###-####. Structural dept and fire marshall are requireing re-location of some exit lights. Called contracotr, no response. 6/6/00 11:26:07 AM
|
ELE00-01642
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | FAIL |
|
|
john ###-#### reinspection NEC: 350-18 MC cable shall be secured within 12" inches of light fixtures, and jboxes of lenths over 6' ft. Corrections posted. Called contractor, left message. 6/6/00 11:27:13 AM
|
ELE00-01777
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | PASS |
|
|
###-#### Branch circuits for 7 A/C compressor units. 6/6/00 11:25:04 AM
|
ELE00-01073
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 06/05/2000 at 08:30:28. Contact: ###-####. No access; left card; called contractor to reschedule 6/6/00 11:25:20 AM
|
ELE00-01822
| Temporary Service | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | FAIL |
|
|
Scott ###-#### NEC: 110 (3) (b). Equipment shall be listed for installation no 'job identification' tag used. Called contracotr. 6/6/00 11:27:59 AM
|
ELE00-00527
| Electrical Rough-In | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 06/05/2000 at 10:39:47. Contact: ###-####. Canopy; corridor ceiling; back offices ele. R/I 6/6/00 11:25:36 AM
|
ELE00-02091
| Final | 6/5/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | PASS |
|
|
judith ###-#### Add kitchen recessed lights. Ele. R/I 6/6/00 11:27:25 AM
|
ELE00-02060
| Rough-In Permanent Service | 6/2/2000 | 6/5/2000 | 6/5/2000 12:00:00 AM | P | CANC |
|
|
craig ###-####\\craig
|