FIR03-00070
| FIR-Aging Inspection | 6/5/2003 | 6/5/2003 | 6/5/2003 12:00:00 AM | | PART |
|
|
work in progress 6/5/2003 7:14:21 AM
|
FIR03-00147
| INSP-Final Inspection | 6/3/2003 | 6/5/2003 | 6/5/2003 12:00:00 AM | A | NR |
|
|
###-#### Mark of Quality called and said they can't locate the approved plans 6/5/2003 5:17:03 PM
|
FIR03-00077
| INSP-Final Inspection | 6/3/2003 | 6/5/2003 | 6/5/2003 12:00:00 AM | P | FAIL |
|
|
###-#### please call 1st troubles tested okay for phone lines, battery loss, ac power; NAC circuit not reporting trouble for circuit #2 as shown on plans appears to be additional EOL on that circuit; need to start testing again after problem is fixed 6/5/2003 5:19:49 PM
|
BLD00-03428
| FIRE-Conference | 6/3/2003 | 6/5/2003 | 6/5/2003 12:00:00 AM | P | FAIL |
|
|
###-#### calvin attempted to test the generator and it failed to provide power when building power was shut off 6/5/2003 5:17:44 PM
|