Inspections for the day of: Thursday, June 5, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00074 FIR-Aging Inspection6/5/20036/5/20036/5/2003 12:00:00 AM NR
Randy Bowron with Debest fire said that they haven't begun to hang pipe yet because the house is not ready yet 6/5/2003 11:04:39 AM
FIR02-00432 INSP-Final Inspection6/4/20036/5/20036/5/2003 12:00:00 AMAFAIL
Provide knox box, provide sign on fire alarm/riser door, clean up all duct detector wiring, rotate sample tube in duct detector in daycare(zone 128), provide filter for duct detector in Joey's Seafood, repair wiring and test hood in the Mongolian BBQ. 6/5/2003 11:07:33 AM
FIR00-00091 INSP-Final Inspection6/5/20036/5/20036/5/2003 12:00:00 AMAPASS
I'm doc finalling this project based on the structural inspector giving it a final occupancy on 9/6/2000. See building permit history
BLD02-02709 FIRE-Final Inspection6/4/20036/5/20036/5/2003 12:00:00 AMPPASS
###-#### kent Fire life safety finaled. No fire alarm and no sprinklers 6/5/2003 11:50:44 AM
BLD03-00300 FIRE-Final Inspection6/5/20036/5/20036/5/2003 12:00:00 AMPFAIL
###-#### Provide current inspection tags for the two fire extinguishers, provide the correct listed eschouceon on the sprinkler pendant outside of the entrance, replace the two painted sprinkler pendants just inside of the entrance, provide missing eschouceon for the pendant in the restroom, provide approved doorhardware on the dressing room doors and door 100, provide verification that the existing hvac unit does not require a duct smoke detector or provide and test, provide testing for the smoke evac system 6/5/2003 2:47:37 PM
BLD02-02610 FIRE-Final Inspection6/5/20036/5/20036/5/2003 12:00:00 AMPPASS
Fire life safety is OK
Gilbert, ###-#### - call 1st so he can meet you there after 4:00 6/5/2003 4:10:24 PM