Inspections for the day of: Monday, June 5, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00118 FIR-Aging Inspection6/5/20066/5/20066/6/2006 11:27:15 AM NR
Dave Maxwell said he would follow up on status of job.
FIR05-00536 INSP-Sprinkler Rough-in6/5/20066/5/20066/6/2006 11:20:19 AMPCANC
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
FIR05-00827 INSP-Sprinkler Rough-in6/5/20066/5/20066/5/2006 3:46:57 PMPPASS
All remaining piping is ok to cover
FIR06-00247 INSP-Final Inspection6/2/20066/5/20066/5/2006 3:45:19 PMPPASS
Permit finaled
MIS06-00133 FIR-Final6/5/20066/5/20066/5/2006 2:26:42 PMPPART
A temporary occupancy was given until a fire extinguisher is provided, remove thumbturn from the north exit and provide indicator, provide approved hardware (lever is ok) on the south exit door, remove or repair the exit sign
MIS06-00132 FIR-Final6/5/20066/5/20066/5/2006 2:26:08 PMPPART
A temporary occupancy was given until a fire extinguisher is provided, remove thumbturn from the north exit and provide indicator, provide approved hardware (lever is ok) on the south exit door.
FIR06-00200 INSP-Sprinkler Rough-in/Hydro6/5/20066/5/20066/5/2006 1:42:41 PMPFAIL
See city approved plans for locations where the upright sprinkler heads are being blocked by steel beams. Additional heads will be required. This inspection was for the overhead shell system piping only and did not include the riser or tenant improvement spaces.
BLD05-03024 FIRE-Final Inspection6/2/20066/5/20066/5/2006 12:09:04 PMACANC
inspection was ment for structural inspector
BLD05-00631 FIRE-Final Inspection6/2/20066/5/20066/5/2006 12:07:26 PMAPASS
life safety passed
BLD05-03414 FIRE-Final Inspection6/2/20066/5/20066/5/2006 10:21:26 AMAPASS
Life safety finaled
FIR06-00044 INSP-Final Inspection6/2/20066/5/20066/5/2006 10:13:48 AMAFAIL
The wrong heads have been installed in the racks, VK100 instead of VK550, provide one additional EQ brace for the main and provide additional heads for the head box.