Inspections for the day of: Thursday, June 5, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00077 INSP-Sprinkler Rough-in6/4/20086/5/20086/5/2008 5:35:13 PMAPART
The lateral earthquake bracing is overspaced. The branchline piping sizing below the mezzanine does not match the approved drawings. This area is a remote area. Resubmitt plans showing the pipe size revisions and revised hydraulic calculations.
BLD07-00143 FIRE-Final Inspection6/4/20086/5/20086/5/2008 5:33:01 PMACANC
Duplicate inspection.
BLD07-00143 FIRE-Final Inspection6/4/20086/5/20086/5/2008 5:31:50 PMAPART
A temporary occupancy was given with Mark Sentenno's permission until the existing school has been demo'd and the new door hardware has been verified.
FIR08-00193 INSP-Final Inspection6/4/20086/5/20086/5/2008 5:29:46 PMAPASS
Permit finaled
BLD07-02067 FIRE-Final Inspection6/4/20086/5/20086/5/2008 11:44:50 AMAPASS
fire life saftey passed
FIR07-00909 INSP-Final Inspection6/4/20086/5/20086/5/2008 11:18:45 AMAPASS
permit finaled
FIR08-00311 INSP-Final Inspection6/5/20086/5/20086/5/2008 10:38:31 AMAPASS
Permit finaled
FIR07-00874 INSP-Sprinkler Rough-in/Hydro6/4/20086/5/20086/5/2008 10:27:52 AMAPART
The 24 hour air tests have been started for the Aid Station with 42psi on the guage and the Dining Area with 47psi on the guage. Test started at 9:00am
BLD05-01603 FIRE-Final Inspection6/4/20086/5/20086/5/2008 10:26:26 AMAPASS
life safety passed
FIR07-00999 INSP-Alarm Testing6/4/20086/5/20086/5/2008 8:55:01 AMAPASS
Permit finaled