ELE09-00972
| Rough-In Permanent Service | 6/5/2009 | 6/5/2009 | 6/5/2009 3:16:12 PM | P | PASS |
|
|
Ok for Id Power to re-connect. Randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s o/h rec. ok
|
ESC09-00156
| General Inspection | 6/5/2009 | 6/5/2009 | 6/5/2009 2:24:59 PM | P | PART |
|
|
ok on going work
|
ELE09-00761
| Final | 6/5/2009 | 6/5/2009 | 6/5/2009 2:23:52 PM | P | FAIL |
|
|
cal Phone #: ###-#### called left message, need to talk with contr, box fill island, shall not use sq D breakers in gould panel ID of cicuits
|
ELE08-02167
| Final | 6/4/2009 | 6/5/2009 | 6/5/2009 1:11:54 PM | P | FAIL |
|
|
I can also be reached at ###-####. Phone #: ###-#### Internet Inspection Request from: andy eckhart 250.8 &110.3(B) use manufactures listed equip grd bus roof switch, fixtures on roof listed for dry location only, 400.8 cords not allowed in raceway blinds
|
ELE08-02839
| Final | 6/4/2009 | 6/5/2009 | 6/5/2009 11:51:07 AM | A | PASS |
|
|
foremans phone TYE ###-#### Phone #: ###-#### Internet Inspection Request from: Bruce Herold ok no card perm. occupancy ok
|
ELE09-00865
| Permanent Service | 6/4/2009 | 6/5/2009 | 6/5/2009 10:34:41 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Murray met contr, needs main p/s outside then address subpanel
|
ELE08-00007
| DOC - Permit Expired | 6/5/2009 | 6/5/2009 | 6/5/2009 10:32:55 AM | A | PASS |
|
|
no action
|
ELE07-00275
| DOC - Permit Expired | 6/5/2009 | 6/5/2009 | 6/5/2009 10:31:49 AM | A | PASS |
|
|
|
ELE09-00938
| Final | 6/3/2009 | 6/5/2009 | 6/5/2009 10:30:52 AM | A | PASS |
|
|
Friday 6/5/09 final inspection for (1)dedicated circuit and (9) smoke detectors. Electrician will not be on site, but can be reached at ###-#### - Brad Phone #: ###-#### Internet Inspection Request from: Carla Ward
|
ELE09-00938
| Electrical Rough-In | 6/5/2009 | 6/5/2009 | 6/5/2009 10:30:37 AM | P | PASS |
|
|
rough in for smoke detectors and dedicated circuit. Please final if possible. thank you Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
|
ELE09-00955
| Electrical Rough-In | 6/4/2009 | 6/5/2009 | 6/5/2009 9:28:38 AM | A | PASS |
|
|
rough in inspection for fire panel. please final at the same time if possible. Please call Brian @ ###-#### when you are on your way and he will meet you there. thank you Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
|
ELE09-00955
| Final | 6/5/2009 | 6/5/2009 | 6/5/2009 9:28:17 AM | A | PASS |
|
|
rough in inspection for fire panel. please final at the same time if possible. Please call Brian @ ###-#### when you are on your way and he will meet you there. thank you Phone #: ###-#### Internet Inspection Request from: Carla Ward
|
ELE09-00959
| Rough-In Permanent Service | 6/4/2009 | 6/5/2009 | 6/5/2009 8:49:42 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/4/2009 at 2:12:58 PM. Contact: ###-####. r/i p/s u/g new ok
|