Inspections for the day of: Monday, June 5, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01652 Final6/4/20176/5/20176/5/2017 3:23:22 PMPPASS
Rock Call when you are on your way.
Thanks
John Phone #: ###-#### Inspection requested via web by John Rourke
Final ok
ELE17-01650 Rough-In Permanent Service6/4/20176/5/20176/5/2017 3:03:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok
ELE17-00699 Final6/5/20176/5/20176/5/2017 1:58:24 PMPPASS
Correction was made thank you. Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
ELE17-01715 Temporary Service6/5/20176/5/20176/5/2017 1:34:15 PMPPASS
Phone #: ###-#### Inspection requested via web by Chris Berthelot
t/s u/g n ok
ELE17-01713 Temporary Service6/5/20176/5/20176/5/2017 1:15:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Chris Berthelot t/s u/g n ok
ELE17-01709 Electrical Rough-In6/5/20176/5/20176/5/2017 9:51:47 AMAPASS
Ready for a cover inspection, ground inspection access to be added later! any other questions plz call me! Thx Steve ###-#### Phone #: ###-#### Inspection requested via web by Steven Meredith
110.3- Square D panel shall only have circuit breakers installed listed for this enclosure.
225.39(D)- Branch circuit for garage with 3 branch circuits shall not be less than 60 amps.
All can be corrected after wall cover is installed.
Garage rough in ok cover
ELE16-03736 Final6/3/20176/5/20176/5/2017 9:06:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Brannon Brown Final ok
ELE17-01657 Final6/2/20176/5/20176/5/2017 8:01:22 AMACANC
Call an hour beforehand to get into the garage Phone #: ###-#### >> Inspection requested via web by Christian Kilpatrick Inspection cancelled from web by: Christian Kilpatrick