Inspections for the day of: Tuesday, June 5, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00500 Final6/5/20186/5/20186/5/2018 2:35:23 PMPPASS
Correction of disposition from original inspection. Final ok
ELE18-01470 Final6/5/20186/5/20186/5/2018 2:12:55 PMPFAIL
Final For Third 3
Request for TCO
Please call Corey Phone #: ###-#### Inspection requested via web by Kevin Perez
Went by Tuesday 2pm to see if could do TCO. Several receptacles not working, open neutral at southwest corner, all ceiling boxes to be covered, misc switch covers missing on line voltage, several covers missing on millwork, some receptacles not trimmed. Will check Wednesday AM.
ELE14-00475 Final6/5/20186/5/20186/5/2018 1:42:49 PMPPASS
Building occupancy changed to a daycare for St. Lukes in 2017 under permit
ELE17-02780. Generator has been removed, no longer on site and finalled. Final ok
ELE17-01337 Electrical Rough-In6/4/20186/5/20186/5/2018 1:27:36 PMAPART
We are requesting a partial final inspection for floors 2, 3, 4, and 5 for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Levels 2 thru 5 checked with items to complete.
518- vanity lights, 503 sparkring, 5th elec. room blanks, breaker blank, 4th- 428 not ready, 419 mirror, 3rd- 328 not ready, check misc tile receptacles for spark rings, 2nd rooms not ready, west storage switch not working, blank cover elevator lobby.
314.20- Discussed if spark rings required for boxes in tile set back a 1/4" or more. Although non combustible as noted spark rings are required.
ELE17-03734 Electrical Rough-In6/4/20186/5/20186/5/2018 9:34:49 AMAPASS
Contact name: Luke Hardy Phone #: ###-#### Inspection requested via web by Clint Tate
Level 1 vestibules and level 2 chase to roof rough in ok cover
ELE18-01789 Permanent Service6/4/20186/5/20186/5/2018 8:40:28 AMAFAIL
Call Troy with any questions
Phone #: ###-#### Inspection requested via web by Don Conley
250.24- A premise wiring system supplied by a grounded AC service shall have a grounding electrode conductor connected to the grounded conductor.