ELE14-00500
| Final | 6/5/2018 | 6/5/2018 | 6/5/2018 2:35:23 PM | P | PASS |
|
|
Correction of disposition from original inspection. Final ok
|
ELE18-01470
| Final | 6/5/2018 | 6/5/2018 | 6/5/2018 2:12:55 PM | P | FAIL |
|
|
Final For Third 3 Request for TCO Please call Corey Phone #: ###-#### Inspection requested via web by Kevin Perez Went by Tuesday 2pm to see if could do TCO. Several receptacles not working, open neutral at southwest corner, all ceiling boxes to be covered, misc switch covers missing on line voltage, several covers missing on millwork, some receptacles not trimmed. Will check Wednesday AM.
|
ELE14-00475
| Final | 6/5/2018 | 6/5/2018 | 6/5/2018 1:42:49 PM | P | PASS |
|
|
Building occupancy changed to a daycare for St. Lukes in 2017 under permit ELE17-02780. Generator has been removed, no longer on site and finalled. Final ok
|
ELE17-01337
| Electrical Rough-In | 6/4/2018 | 6/5/2018 | 6/5/2018 1:27:36 PM | A | PART |
|
|
We are requesting a partial final inspection for floors 2, 3, 4, and 5 for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Levels 2 thru 5 checked with items to complete. 518- vanity lights, 503 sparkring, 5th elec. room blanks, breaker blank, 4th- 428 not ready, 419 mirror, 3rd- 328 not ready, check misc tile receptacles for spark rings, 2nd rooms not ready, west storage switch not working, blank cover elevator lobby. 314.20- Discussed if spark rings required for boxes in tile set back a 1/4" or more. Although non combustible as noted spark rings are required.
|
ELE17-03734
| Electrical Rough-In | 6/4/2018 | 6/5/2018 | 6/5/2018 9:34:49 AM | A | PASS |
|
|
Contact name: Luke Hardy Phone #: ###-#### Inspection requested via web by Clint Tate Level 1 vestibules and level 2 chase to roof rough in ok cover
|
ELE18-01789
| Permanent Service | 6/4/2018 | 6/5/2018 | 6/5/2018 8:40:28 AM | A | FAIL |
|
|
Call Troy with any questions Phone #: ###-#### Inspection requested via web by Don Conley 250.24- A premise wiring system supplied by a grounded AC service shall have a grounding electrode conductor connected to the grounded conductor.
|