Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00686 Final6/5/20186/5/20186/5/2018 2:00:18 PMPPASS
Homeowner should be there Phone #: ###-#### Inspection requested via web by Troy Cobb...ok to final
ELE18-01087 Final6/4/20186/5/20186/5/2018 1:51:33 PMPPASS
Power to CNC in 2025 Century Way. Phone #: ###-#### Inspection requested via web by Steve Blackmer...job complete...OCPD and disconnect ok...ok to final
ELE18-01087 Electrical Rough-In6/5/20186/5/20186/5/2018 1:50:40 PMPPASS
Power to CNC in 2025 Century Way. Phone #: ###-#### Inspection requested via web by Steve Blackmer...disconnect at service...piped thru building to disconnect at machine...ok
ELE18-01389 Final6/5/20186/5/20186/5/2018 12:01:18 PMPPASS
Old location is 10353 Fairview Phone #: ###-#### Inspection requested via web by Steve VanWinkle...no corrections needed...inspected wrong address for previous location of sign...ok to final permit
ELE18-01719 Conference6/4/20186/5/20186/5/2018 11:19:44 AMAPASS
Please call 30min before dropping by. Phone #: ###-#### Inspection requested via web by Lee Coulson...discussed wiring of basement...living rm, bathroom, and 2 bedrooms...using existing circuits...placing arc fault on one circuit to satisfy requirement for bedroom...pamphlet given...homeowner competent in work
ELE18-01894 Rough-In Permanent Service6/4/20186/5/20186/5/2018 9:19:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn....rough ok to cover...p/s u/g new ok
ELE18-00810 Final6/4/20186/5/20186/5/2018 8:54:00 AMAFAIL
should be open Phone #: ###-#### Inspection requested via web by Brad Baker...
1. bath instahot needs to be a 30A circuit per manufacturers rating...110.3
2. panel labelling needs completed...408.4
3. outlets within 6' of sink shall have GFCI protection...breakroom future sink..210.8(B)(5)
4. west wall GFCI has no power...unlabelled circuit in panel??