Inspections for the day of: Friday, June 5, 2020.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-02004 Final6/4/20206/5/20206/5/2020 3:39:03 PMPPASS
owner: Dan Malloy ###-####
Field Super: Chad Robertson ###-#### Phone #: ###-#### Inspection requested via web by Lisa Whitney- furnace a/c coil co locking caps ok
MEC20-02230 Final6/4/20206/5/20206/5/2020 3:13:04 PMPNR
Please call Robert on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- still installing- reschedule
MEC20-02152 Rough-in6/1/20206/5/20206/5/2020 2:57:05 PMPNR
TYLER ###-####, PLEASE CALL FOR ACCESS Phone #: ###-#### Inspection requested via web by Mike Almanza- still installing- thimble not firecaulked properly- installer will fix
MEC20-02147 Final6/1/20206/5/20206/5/2020 2:20:22 PMPPASS
LOCK BOX 1278 - EMPTY HOME
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok
MEC20-02251 Final6/4/20206/5/20206/5/2020 1:58:15 PMPNR
Please call Steven on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- still installing- reschedule
MEC20-00984 Final6/5/20206/5/20206/5/2020 1:39:09 PMPFAIL
garage doors will be open Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7238 need gas piping completed to furnace- verify gas valves to fireplaces are turned on- 7252 ok
MEC20-00879 Final6/5/20206/5/20206/5/2020 1:37:01 PMPFAIL
garage doors will be open Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7200 needs condenser pad leveled- 7226 need pvc intake supported and leveled horizontally- verify gas valves are on on fireplaces
MEC20-00985 Final6/5/20206/5/20206/5/2020 1:35:15 PMPPASS
garage doors will be open, super will be on job site all day Phone #: ###-#### Inspection requested via web by Oleg Chervak- final both units ok
MEC20-02243 Final6/4/20206/5/20206/5/2020 1:02:36 PMPNH
Please call Tanner on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no one home- no installer onsite- Tanner on different job per phone call- reschedule
MEC20-02170 Final6/4/20206/5/20206/5/2020 12:48:19 PMPFAIL
John Piper ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok- need locking caps on a/c service ports- need primary condensate drain ran in 3/4" pvc with grade from pump location to outside and extend down to bottom of wood siding-use minimal vinyl tubing from pump to pvc- send pic for reinspect
PLM20-02175 Water Heater Final6/3/20206/5/20206/5/2020 12:24:29 PMPPASS
Homeowner Michelle Balliett ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- w/h co ok
MEC20-02076 Final6/3/20206/5/20206/5/2020 12:24:03 PMPPASS
Homeowner Michelle Balliett ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co locking caps ok
MEC20-01591 Rough-in6/4/20206/5/20206/5/2020 11:21:08 AMANR
Phone #: ###-#### Inspection requested via web by Debbie Marino- both units need completed- Steven was onsite and went over with him- recall in when ready
MEC20-01591 Pressure Test6/4/20206/5/20206/5/2020 11:20:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass both units for houses only- will need to see underground from meter bar location to east unit- tagged gas piping
MEC20-02135 Final6/2/20206/5/20206/5/2020 10:15:17 AMAPASS
Please call Brent prior to arrival at ###-####. Phone #: ###-#### Inspection requested via web by Andrea Grigsby- furnace a/c coil co locking caps ok
MEC20-01746 Final6/1/20206/5/20206/5/2020 9:35:03 AMPCANC
Please call Mariam (homeowner) when you are on the way. Phone #: ###-#### >> Inspection requested via web by Brett Shannon Inspection cancelled from web by: Brett Shannon
MEC20-02213 Final6/4/20206/5/20206/5/2020 9:22:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Newkirk- need to provide co detector near bedrooms- single wall flue off furnace needs 6" clearnce to sheetrock and wood moulding around door- recall in when ready
MEC20-02255 Rough-in6/5/20206/5/20206/5/2020 8:53:58 AMPFAIL
Site Contact - Renato Albanese Phone #: ###-#### Inspection requested via web by RM Mechanical- need to bepulled under a plumbing permit not mechanical
MEC20-02187 Final6/4/20206/5/20206/5/2020 8:41:04 AMACANC
We are sending pictures of corrections made to pass this permit. Should have been sent 06/04/20 in the PM to Brian Scoles. Phone #: ###-#### Inspection requested via web by Arielle Hendricks- this permit was finaled out on 6-4-20
MEC19-03677 Mec-Aging Inspection6/5/20206/5/20206/5/2020 7:45:34 AM FAIL
needs final inspection- BLD still open
MEC19-04637 Mec-Aging Inspection6/5/20206/5/20206/5/2020 7:44:41 AM CANC
needs called in for inspection when ready- WIP
MEC19-03673 Mec-Aging Inspection6/5/20206/5/20206/5/2020 7:43:31 AM CANC
expired permit
MEC19-03673 DOC - Permit Expired6/5/20206/5/20206/5/2020 7:43:10 AMAPASS
no calls no activity permit expired