MEC20-01413
| Final | 6/4/2020 | 6/5/2020 | 6/5/2020 3:43:08 PM | P | PASS |
|
|
Please call prior to heading out ###-####. Please give 30 heads up. Would prefer closer to 4. Phone #: ###-#### Inspection requested via web by Ashley Van Cleave
|
MEC20-02166
| Final | 6/4/2020 | 6/5/2020 | 6/5/2020 3:42:58 PM | P | PASS |
|
|
Call ahead to Michael @ ###-#### when headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small
|
MEC20-02167
| Final | 6/2/2020 | 6/5/2020 | 6/5/2020 3:38:35 PM | P | PASS |
|
|
INSTALLER AL ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
MEC20-02089
| Rough-in | 6/5/2020 | 6/5/2020 | 6/5/2020 3:01:04 PM | P | PASS |
|
|
Cover Inspection Please contact John Shartzer prior to arrival Phone #: ###-#### Inspection requested via web by Commercial Coordinator - above hard lids 1st floor okay
|
MEC20-02052
| Pressure Test | 6/5/2020 | 6/5/2020 | 6/5/2020 2:46:58 PM | P | CANC |
|
|
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney - schedualed by mistake
|
MEC19-04496
| Final | 6/4/2020 | 6/5/2020 | 6/5/2020 1:43:13 PM | P | FAIL |
|
|
Can you call Garrit at ###-#### before you go. He will need to be there to let you in. Phone #: ###-#### Inspection requested via web by Kristy Newkirk - please add new erv to permit, I dont need to go back, - reschedual and ill pass it
|
MEC19-00377
| Mec-Aging Inspection | 6/5/2020 | 6/5/2020 | 6/5/2020 11:00:18 AM | | CANC |
|
|
wip
|
MEC20-01851
| Final | 6/4/2020 | 6/5/2020 | 6/5/2020 10:42:20 AM | A | FAIL |
|
|
Homeowner George Rogers ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - condencer needs locking caps - send picture for re-inspection
|
MEC20-02090
| Rough-in | 6/4/2020 | 6/5/2020 | 6/5/2020 10:21:47 AM | A | FAIL |
|
|
Please contact GM Jordan if any questions arise at the job site. Phone #: ###-#### Inspection requested via web by Ashley Van Cleave - range duct rough-in not complete - manual j shows pantry with a supply and return please revise manual j - there is a open supply run in the crawl
|
MEC20-01904
| Rough-in | 6/4/2020 | 6/5/2020 | 6/5/2020 9:48:05 AM | A | FAIL |
|
|
Garage Code: 3517 - Builder: ###-#### - HVAC: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - flue tests in basement at zero - fresh air 2nd floor to return plenum, not return can in master closet, that return not shown on manual j
|
MEC20-01904
| Pressure Test | 6/4/2020 | 6/5/2020 | 6/5/2020 9:45:35 AM | A | PASS |
|
|
Garage Code: 3517 - Builder: ###-#### - HVAC: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks -60lb, - 5lb 2nd floor
|
MEC19-05384
| Rough-in | 6/4/2020 | 6/5/2020 | 6/5/2020 9:17:58 AM | A | PASS |
|
|
flue test Phone #: ###-#### Inspection requested via web by Brandon Sorensen -5lb x8
|