Inspections for the day of: Monday, June 6, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01970 Final6/6/20056/6/20056/6/2005 4:40:35 PMPPASS
We relocated existing receptacle wiring and 3-way switch wiring to allow the framing-in of a new window. Please call Mike @ ###-#### when you are headed that way. THANKS!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
ELE05-01963 Final6/6/20056/6/20056/6/2005 4:07:47 PMPPASS
We installed PVC pipe and wiring to a new post light & photocell. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
ELE05-01962 Final6/6/20056/6/20056/6/2005 3:05:16 PMPPASS
We hard-wired a sprinkler clock. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
ELE05-01960 Permanent Service6/6/20056/6/20056/6/2005 3:04:02 PMPPASS
###-#### kevin///homeowner will be there////access from fairview across from gold's gym new panel ok
ELE05-01950 Temporary Service6/6/20056/6/20056/6/2005 1:46:38 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohl corrections made t/s u/g n ok
ELE05-01961 Temporary Service6/6/20056/6/20056/6/2005 1:14:58 PMPPASS
###-#### dan t/s u/g n ok
ELE05-01814 Conference6/6/20056/6/20056/6/2005 12:25:37 PMPCANC
Scheduled by a contractor via Hello! on 6/6/2005 at 10:34:37 AM. Contact: ###-####. see ri inspection
ELE05-01613 Final6/6/20056/6/20056/6/2005 10:27:23 AMAFAIL
Scheduled by a contractor via Hello! on 6/6/2005 at 7:17:03 AM. Contact: ###-####. called left message, left corr notice, 110.2 equipment shall be approved, listed, 230.2 shall supply branch circuits via a service
ELE05-01951 Electrical Rough-In6/3/20056/6/20056/6/2005 9:55:47 AMAFAIL
###-#### called, no answer, left corr notice, 210.52(D) bath recpts shall be within 3' of basin, 210.52(A)(2) recpts shall be installed in wall space over 2'-0", 300.4(A)(1) bored hole shall be 1 1/4" from edge of framing member,300.4(B)(2) nm cable shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished surface,314.15(A) fittings shall be listed for use in wet locations,210.70(A)(2) switch for stairs shall be provided at each level. BCC all make-up shall be done, job id sticker shall be posted, approved set of plans shall be on job
ELE05-01923 Electrical Rough-In6/2/20056/6/20056/6/2005 9:04:23 AMAPASS
Scheduled by a contractor via Hello! on 6/2/2005 at 11:29:11 AM. Contact: ###-####. ric walls only ok
ELE05-01944 Temporary Service6/3/20056/6/20056/6/2005 8:33:19 AMAPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g n ok
ELE05-01772 Temporary Service6/3/20056/6/20056/6/2005 8:18:25 AMAPASS
rob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g n ok
ELE05-01814 Electrical Rough-In6/6/20056/6/20056/6/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 6/6/2005 at 10:34:37 AM. Contact: ###-####. ok to cover u/g in house panel area