ELE05-01970
| Final | 6/6/2005 | 6/6/2005 | 6/6/2005 4:40:35 PM | P | PASS |
|
|
We relocated existing receptacle wiring and 3-way switch wiring to allow the framing-in of a new window. Please call Mike @ ###-#### when you are headed that way. THANKS!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE05-01963
| Final | 6/6/2005 | 6/6/2005 | 6/6/2005 4:07:47 PM | P | PASS |
|
|
We installed PVC pipe and wiring to a new post light & photocell. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE05-01962
| Final | 6/6/2005 | 6/6/2005 | 6/6/2005 3:05:16 PM | P | PASS |
|
|
We hard-wired a sprinkler clock. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE05-01960
| Permanent Service | 6/6/2005 | 6/6/2005 | 6/6/2005 3:04:02 PM | P | PASS |
|
|
###-#### kevin///homeowner will be there////access from fairview across from gold's gym new panel ok
|
ELE05-01950
| Temporary Service | 6/6/2005 | 6/6/2005 | 6/6/2005 1:46:38 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl corrections made t/s u/g n ok
|
ELE05-01961
| Temporary Service | 6/6/2005 | 6/6/2005 | 6/6/2005 1:14:58 PM | P | PASS |
|
|
###-#### dan t/s u/g n ok
|
ELE05-01814
| Conference | 6/6/2005 | 6/6/2005 | 6/6/2005 12:25:37 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 6/6/2005 at 10:34:37 AM. Contact: ###-####. see ri inspection
|
ELE05-01613
| Final | 6/6/2005 | 6/6/2005 | 6/6/2005 10:27:23 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/6/2005 at 7:17:03 AM. Contact: ###-####. called left message, left corr notice, 110.2 equipment shall be approved, listed, 230.2 shall supply branch circuits via a service
|
ELE05-01951
| Electrical Rough-In | 6/3/2005 | 6/6/2005 | 6/6/2005 9:55:47 AM | A | FAIL |
|
|
###-#### called, no answer, left corr notice, 210.52(D) bath recpts shall be within 3' of basin, 210.52(A)(2) recpts shall be installed in wall space over 2'-0", 300.4(A)(1) bored hole shall be 1 1/4" from edge of framing member,300.4(B)(2) nm cable shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished surface,314.15(A) fittings shall be listed for use in wet locations,210.70(A)(2) switch for stairs shall be provided at each level. BCC all make-up shall be done, job id sticker shall be posted, approved set of plans shall be on job
|
ELE05-01923
| Electrical Rough-In | 6/2/2005 | 6/6/2005 | 6/6/2005 9:04:23 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/2/2005 at 11:29:11 AM. Contact: ###-####. ric walls only ok
|
ELE05-01944
| Temporary Service | 6/3/2005 | 6/6/2005 | 6/6/2005 8:33:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g n ok
|
ELE05-01772
| Temporary Service | 6/3/2005 | 6/6/2005 | 6/6/2005 8:18:25 AM | A | PASS |
|
|
rob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g n ok
|
ELE05-01814
| Electrical Rough-In | 6/6/2005 | 6/6/2005 | 6/6/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/6/2005 at 10:34:37 AM. Contact: ###-####. ok to cover u/g in house panel area
|