BLD04-01705
| FIRE-Final Inspection | 6/6/2005 | 6/6/2005 | 6/6/2005 4:01:58 PM | P | PART |
|
|
Final pending fire alarm sign off.
|
FIR05-00208
| INSP-Sprinkler Rough-in | 6/3/2005 | 6/6/2005 | 6/6/2005 1:37:10 PM | P | FAIL |
|
|
Upright heads in open space adjacent to new tenant demising wall are overspaced. Provide complete coverage as required by review notes.
|
FIR05-00205
| INSP-Final Inspection | 6/3/2005 | 6/6/2005 | 6/6/2005 10:48:45 AM | A | FAIL |
|
|
Add smoke detection in room 118, add notification in office room 104 per note #7 on review comments, provide updated map at FACP, provide sign at room door containing FACP, adjust heights on AV's to meet reqirements of note #10.
|
FIR04-00724
| INSP-Supply line flush | 6/3/2005 | 6/6/2005 | 6/6/2005 10:41:31 AM | A | CANC |
|
|
Cancel inspection per Bruce with Commercial Fire protection.
|
FIR05-00152
| INSP-Sprinkler Rough-in | 6/6/2005 | 6/6/2005 | 6/6/2005 12:00:00 AM | P | PART |
|
|
Underground fire supply line OK to cover up to point installed at 3rd column line from north side of hotel.
|