ELE06-02053
| Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 4:18:14 PM | P | PART |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Darla Downs u/g for tank monitor system ok
|
ELE06-01807
| Electrical Rough-In | 6/6/2006 | 6/6/2006 | 6/6/2006 3:35:58 PM | P | FAIL |
|
|
Ceiling rough-in. Please call 1/2 hour before arrive to arrange to meet. Contact Jim @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie corr. called 760.2, 780.2, 800.2 abandoned cables, 800.21,24, 760.7,8, 770.21,24 cable laying on not supported as 300.11 states also same for high volt cables, 110.12(A) seal all unused KOs and fittings, 330.30 secure MC as code noted states, 314.25 covers for all boxes, BCC no violations to be retained
|
ELE06-01000
| Temporary Service | 6/6/2006 | 6/6/2006 | 6/6/2006 2:22:12 PM | P | PASS |
|
|
re-insp t/p ###-####- wayne t/s o/h new ok
|
ELE06-01898
| Electrical Rough-In | 6/6/2006 | 6/6/2006 | 6/6/2006 1:45:28 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 6/6/2006 at 8:54:56 AM. Contact: ###-####. all u/g complete r/i ok
|
ELE05-03535
| Final | 6/6/2006 | 6/6/2006 | 6/6/2006 1:03:46 PM | P | FAIL |
|
|
nickoly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner not all corrections made and new ones created, 300.14 6 ' free conductor, upstairs hall left of stairs, 110.14(B) needs splicing device grds at garage fixtures, 314.16& 43, upstairs bed rm top of stairs left, and hall box fill and screws inplastic box, 110.3(A&B) replace boxes in M bed rm and den where holes are drilled and boxes are damaged
|
ELE06-01695
| Final | 6/5/2006 | 6/6/2006 | 6/6/2006 10:51:57 AM | A | PASS |
|
|
My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok
|
ELE06-02056
| Final | 6/5/2006 | 6/6/2006 | 6/6/2006 10:14:20 AM | A | FAIL |
|
|
A/C ready for final. Please contact Patrick Gill, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr. called a/c ok but subpanel where a/c is feed from and p/s are a mess work done by owner or contractor dought if there was permit or inspection, BCC no violation retained250.52,104 grd or bond p/s to water, 250.24(A)(5) isolate grds neutrals suubpanel, 312.5 conn for all cables, 110.12(A) seal unused openings, 240.51,52,53,54 shall install type S fuses and adapters where abuse over fusing circuits, 300.4(F) bushings for 4 and larger in raceways, 300.10 bond bushings where RE washers are used, 408.4 circut directory, 314.29 I think there is a buried LB or box behind p/s, or it might be open wiring
|
ELE06-02058
| Permanent Service | 6/5/2006 | 6/6/2006 | 6/6/2006 9:19:45 AM | A | FAIL |
|
|
andy - sapce #5; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley grd rod closer than 6ft disconnect over 30 ft from trailer, too many 90s in u/g called
|
ELE06-02013
| Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 8:49:57 AM | A | PART |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy r/i walls ok
|
ELE06-01970
| Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 8:15:54 AM | A | PART |
|
|
slab inspection//ron wymer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles inspection for electrode only
|