Inspections for the day of: Tuesday, June 6, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02053 Electrical Rough-In6/5/20066/6/20066/6/2006 4:18:14 PMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Darla Downs
u/g for tank monitor system ok
ELE06-01807 Electrical Rough-In6/6/20066/6/20066/6/2006 3:35:58 PMPFAIL
Ceiling rough-in. Please call 1/2 hour before arrive to arrange to meet. Contact Jim @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie corr. called 760.2, 780.2, 800.2 abandoned cables, 800.21,24, 760.7,8, 770.21,24 cable laying on not supported as 300.11 states also same for high volt cables, 110.12(A) seal all unused KOs and fittings, 330.30 secure MC as code noted states, 314.25 covers for all boxes, BCC no violations to be retained
ELE06-01000 Temporary Service6/6/20066/6/20066/6/2006 2:22:12 PMPPASS
re-insp t/p ###-####- wayne t/s o/h new ok
ELE06-01898 Electrical Rough-In6/6/20066/6/20066/6/2006 1:45:28 PMPPART
Scheduled by a contractor via Hello! on 6/6/2006 at 8:54:56 AM. Contact: ###-####. all u/g complete r/i ok
ELE05-03535 Final6/6/20066/6/20066/6/2006 1:03:46 PMPFAIL
nickoly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. met owner not all corrections made and new ones created, 300.14 6 ' free conductor, upstairs hall left of stairs, 110.14(B) needs splicing device grds at garage fixtures, 314.16& 43, upstairs bed rm top of stairs left, and hall box fill and screws inplastic box, 110.3(A&B) replace boxes in M bed rm and den where holes are drilled and boxes are damaged
ELE06-01695 Final6/5/20066/6/20066/6/2006 10:51:57 AMAPASS
My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok
ELE06-02056 Final6/5/20066/6/20066/6/2006 10:14:20 AMAFAIL
A/C ready for final. Please contact Patrick Gill, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr. called a/c ok but subpanel where a/c is feed from and p/s are a mess work done by owner or contractor dought if there was permit or inspection, BCC no violation retained250.52,104 grd or bond p/s to water, 250.24(A)(5) isolate grds neutrals suubpanel, 312.5 conn for all cables, 110.12(A) seal unused openings, 240.51,52,53,54 shall install type S fuses and adapters where abuse over fusing circuits, 300.4(F) bushings for 4 and larger in raceways, 300.10 bond bushings where RE washers are used, 408.4 circut directory, 314.29 I think there is a buried LB or box behind p/s, or it might be open wiring
ELE06-02058 Permanent Service6/5/20066/6/20066/6/2006 9:19:45 AMAFAIL
andy - sapce #5; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley grd rod closer than 6ft disconnect over 30 ft from trailer, too many 90s in u/g called
ELE06-02013 Electrical Rough-In6/5/20066/6/20066/6/2006 8:49:57 AMAPART
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy
r/i walls ok
ELE06-01970 Electrical Rough-In6/5/20066/6/20066/6/2006 8:15:54 AMAPART
slab inspection//ron wymer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles inspection for electrode only