Inspections for the day of: Tuesday, June 6, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00425 INSP-Sprinkler Rough-in/Hydro6/5/20066/6/20066/7/2006 10:24:12 AMAPART
Overhead inspection for the 1st floor hotel lobby soffits, 9th floor main, 10th and 11th floors performed today. The 1st floor soffits are okay to cover-corrections have been completed, 9th floor is acceptable to cover, 10th floor installation is okay-still need to fire caulk wall penetrations prior to cover. The 11th floor failed due to missing EQ brace, overspaced heads at three locations, missing upright at SE stair landing.
FIR06-00392 INSP-Sprinkler Rough-in/Hydro6/5/20066/6/20066/6/2006 4:00:59 PMPPART
Inspection for area 2 as marked on approved plans is acceptable for cover.
FIR06-00305 INSP-Final Inspection6/2/20066/6/20066/6/2006 3:59:54 PMAFAIL
Sample tubes must meet mfg. specifications for the correct size, spacing, number of perforations, and length of tube installed corresponding to the ductwork employed.
FIR06-00401 INSP-Final Inspection6/5/20066/6/20066/6/2006 1:42:44 PMPNR
Project was unfinished and work still in progress at the time of field inspection approx. 1:30 pm. Notified Mike with Shilo to reschedule when work is completed.
FIR06-00404 INSP-Final Inspection6/6/20066/6/20066/6/2006 1:15:45 PMPPASS
Required corrections have been made, fire sprinkler permit finaled.
BLD06-00826 FIRE-Final Inspection6/6/20066/6/20066/6/2006 12:33:58 PMPPASS
Items on correction notice have been completed, inspection passed.
BLD06-00324 FIRE-Final Inspection6/5/20066/6/20066/6/2006 12:01:48 PMAFAIL
Need to provide a fire extinguisher with current tag installed as discussed, one exit sign is blocked and will need to be relocated, door hardware at one location will need to be changed, still need to test emergency lighting for the path of egress.
FIR06-00316 INSP-Final Inspection6/5/20066/6/20066/6/2006 11:07:28 AMAPASS
Fire alarm finaled.