Inspections for the day of: Wednesday, June 6, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00103 INSP-Sprinkler Rough-in6/5/20076/6/20076/7/2007 10:12:31 AMPFAIL
Rough Inspection for the 5th floor installation was ok but the plans need to be resubmitted due to riser nipples being added to the gridded system. I also inspected both standpipes except for the roof manifold and the 5th floor riser.
FIR06-00602 INSP-Final Inspection6/5/20076/6/20076/7/2007 9:41:50 AMAFAIL
See mike timmerman's review comments
FIR07-00155 INSP-Supply line flush6/5/20076/6/20076/6/2007 5:26:48 PM DONE
See sam rogers inspection review comments for todays date.
FIR06-00985 INSP-Sprinkler Rough-in6/5/20076/6/20076/6/2007 5:00:42 PMPCANC
No time for rough-in inspection due to time constraints. Jeff stated he would call it back in.
FIR05-00536 INSP-Sprinkler Rough-in6/6/20076/6/20076/6/2007 4:58:53 PMPPASS
See the city approved plans for areas where piping is ok to cover
MIS07-00124 FIR-Final6/6/20076/6/20076/6/2007 2:44:43 PMPFAIL
This inspection ended up being a conference since the property manager was unable to test the emergency lights and exit signs. The Right Aid and the Animal Hospital both need sprinkler work done due to overspacing issues. The Optical shop needs exit door hardware addressed. Right Aid has the west front exit blocked with displays and no exit sign as per the approved plans.....ect. This inspection was basically a starting point and not a complete inspection for the owner and I stated this as well. The Right Aid inspection was the only one called in.
FIR06-00800 INSP-Final Inspection6/5/20076/6/20076/6/2007 12:56:40 PMACANC
This inspection is being cancelled until forrest is back. Sam rogers contacted the contractor.
FIR06-00985 INSP-Supply line flush6/5/20076/6/20076/6/2007 12:49:45 PMPPASS
UG flush passed
FIR07-00102 INSP-Sprinkler Rough-in/Hydro6/5/20076/6/20076/6/2007 12:36:36 PMPPASS
Underground hydro test passed.
FIR06-00007 INSP-Final Inspection6/5/20076/6/20076/6/2007 12:33:36 PMACANC
Forrest, pls call when on your way. JB needs about a 30 min notice. Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
BLD07-00535 FIRE-Final Inspection6/5/20076/6/20076/6/2007 12:32:15 PMAFAIL
Provide correct door hardware from the warehouse that allows free passage as discussed
BLD07-01201 FIRE-Final Inspection6/5/20076/6/20076/6/2007 9:55:01 AMAPART
Todays inspection was only for the 10488 address. Insulation backing appeared to be mounted ok.
FIR07-00352 INSP-Sprinkler Rough-in6/5/20076/6/20076/6/2007 9:52:42 AMAPASS
Previous inspection gave ok to cover.
FIR07-00393 INSP-Sprinkler Rough-in6/5/20076/6/20076/6/2007 9:51:54 AMAPASS
Full height wall has been removed. Ok to cover.
FIR07-00397 INSP-Sprinkler Rough-in6/5/20076/6/20076/6/2007 9:48:00 AMAPASS
Corrections have been made. Ok to cover.
FIR07-00311 INSP-Final Inspection6/5/20076/6/20076/6/2007 9:46:56 AMAFAIL
Did not do a final inspection because a rough-in has not been done and there are no approved plans on site. I contacted Ron with Viking and let him know this.
FIR07-00438 INSP-Final Inspection6/5/20076/6/20076/6/2007 8:32:34 AMAPASS
permit finaled