Inspections for the day of: Friday, June 6, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00344 FIRE-Final Inspection6/6/20086/6/20086/6/2008 2:23:11 PMPPASS
Kil- fire life saftey Phone #: ###-####
BLD07-03193 FIRE-Final Inspection6/6/20086/6/20086/6/2008 2:22:52 PMPPART
Still need site work complete at both entrances-paving is not finished-need to comply with fire department access requirements-see fire code review notes for specific details.
FIR07-00606 INSP-Sprinkler Rough-in6/5/20086/6/20086/6/2008 2:15:50 PMAFAIL
Overhead rough-in inspection for the auditoruim area failed due to overspaced upright heads, missing coverage at the SW stair landing, provide flexible couplings at the 4' main where lacking correct seismic clearance at the block walls east and west sides, noted changes in pipe routing of the 4" main not indicated on plans at the intersection of the catwalk and cross main, the north half of the pendent heads at cloud ceilings are not yet complete, noted site made EQ braces consisting of unistrut and bent 3/8" all-thread rod attatched to truss webs are not approved or listed for this use-provide materials and components installed in such a way to meet appropriate guidelines per NFPA 13.
FIR08-00334 INSP-Final Inspection6/5/20086/6/20086/6/2008 1:45:19 PMAPASS
Fire alarm testing passed, one notification appliance at the mens restroom properly secured while on site, permit finaled.
BLD08-00011 FIRE-Final Inspection6/6/20086/6/20086/6/2008 12:31:00 PMPDEFR
vince - fire life safety Phone #: ###-####
FIR08-00361 INSP-Sprinkler Rough-in6/5/20086/6/20086/6/2008 11:37:44 AMAFAIL
The second floor middle and left end units have been sheetrocked prior to overhead rough-in inspection, completed satisfactory flow testing and OH inspection for the right side unit 1st and 2nd floors, noted missing flow switch and outside bell at all units, discussed shoutoff valve signage and head box placement.
BLD08-00925 FIRE-Alarm Testing6/5/20086/6/20086/6/2008 10:05:45 AMAFAIL
Lacking the required fire alarm permit for interconnection of the existing building fire alarm system to the new hood suppression equipment per IFC and NFPA 72-see also attatched fire code review notes for details. Noted alarm work has been completed without a permit and will incur double fees.
FIR07-00879 INSP-Sprinkler Rough-in/Hydro6/4/20086/6/20086/6/2008 9:37:25 AMPNR
Not ready for inspection per contractor due to lacking water supply.
FIR08-00376 INSP-Sprinkler Rough-in6/5/20086/6/20086/6/2008 9:23:36 AMAPART
Approved for cover at the drop ceiling areas within the tenant remodel.
FIR07-00879 INSP-Supply line flush6/4/20086/6/20086/6/2008 9:15:34 AMPCANC
This is an ug flush. I have a hydro scheduled for earlier this day also. Brian D is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus
BLD08-00127 FIRE-Final Inspection6/6/20086/6/20086/6/2008 9:11:57 AMPCANC
Scheduled by a contractor via Hello! on 6/6/2008 at 6:53:19 AM. Contact: ###-####.
FIR08-00155 FIR-Aging Inspection6/6/20086/6/20086/6/2008 8:06:45 AM DONE
Pending site inspection request.