FIR08-00351
| INSP-Sprinkler Rough-in/Hydro | 6/5/2008 | 6/6/2008 | 6/6/2008 4:25:18 PM | P | CANC |
|
|
Overbooked. Will need to reschedule
|
FIR08-00094
| INSP-Alarm Testing | 6/5/2008 | 6/6/2008 | 6/6/2008 4:12:52 PM | P | DONE |
|
|
Partial Inspection. Todays inspection was for the new north wing addition and the new south wing addition. Everything tested satifactory except the fire doors in the south wing were not ready to be tested yet.
|
FIR07-00874
| INSP-Sprinkler Rough-in/Hydro | 6/6/2008 | 6/6/2008 | 6/6/2008 4:11:10 PM | P | PASS |
|
|
24 hour air test for the Dining Area and the Aid Station has passed
|
BLD08-00125
| FIRE-Final Inspection | 6/5/2008 | 6/6/2008 | 6/6/2008 4:08:21 PM | P | FAIL |
|
|
Overbooked and the project related fire alarm permit is not ready.
|
FIR08-00317
| INSP-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 3:03:42 PM | P | CANC |
|
|
Overbooked. Will need to be rescheduled.
|
BLD08-00063
| FIRE-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 2:17:12 PM | P | FAIL |
|
|
provide occupant load sign
|
BLD08-00062
| FIRE-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 2:16:29 PM | P | PASS |
|
|
fire life saftey passed
|
BLD07-02391
| FIRE-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 12:00:59 PM | P | FAIL |
|
|
Resubmit plans showing the scope of work changing or finish building the interior walls. Provide an emergency light/exit sign at the exit door to the finished tenant as per the plans. Provide a fire extinguisher in the hall as per the plans. Provide power to the south duct smoke detector so it can be tested. The north smoke detector tested ok.
|
BLD07-02352
| FIRE-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 11:33:45 AM | P | PASS |
|
|
Life safety passed
|
BLD08-00651
| FIRE-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 9:24:56 AM | P | PASS |
|
|
life safety passed
|
FIR08-00231
| INSP-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 8:09:20 AM | P | CANC |
|
|
Troy, please call as soon as you know an approximate time. Thank You. ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
FIR08-00094
| INSP-Alarm Testing | 6/5/2008 | 6/6/2008 | 6/5/2008 10:30:32 PM | A | CANC |
|
|
Customer looking for temp CO. Phone #: ###-#### Internet Inspection Request from: Robert Gobler Inspection cancelled from web by: Robert Gobler
|