Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00564 FIRE-Final Inspection6/6/20126/6/20126/6/2012 3:52:00 PMPPASS
Life safety passed.
BLD12-01157 FIRE-Final Inspection6/6/20126/6/20126/6/2012 2:48:05 PMPFAIL
Resubmit plans showing the actual wall layout for the kitchen area. The sprinkler system requires modifications in the kitchen, dining, corridor and cooler areas. The smoke detectos appear to be overspaced. A fire alarm contractor needs to provide verificaiton the system met code when installed or provide modifications. The fire alarm system may need to be upgraded due to occupancy type and occupant load changes. Tim in plan review, David the owner and myself discussed this and I provided phone numbers to plan review.
BLD12-00294 FIRE-Final Inspection6/5/20126/6/20126/6/2012 1:53:04 PMAFAIL
The racks along the east wall exceed 10' in height (12'-0") and they have not been placed 3" off this same wall as the plans show. They have been place 30" off of the face of the two columns. Plans need to be resubmitted showing the actual layout and racking height utilized.