Inspections for the day of: Thursday, June 6, 2013.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00530 ELE-Aging Inspection6/6/20136/6/20136/6/2013 4:01:21 PM DONE
contractor to call for final
ELE12-00194 ELE-Aging Inspection6/6/20136/6/20136/6/2013 3:50:51 PM DONE
waiting on owner
ELE13-01411 Electrical Rough-In6/6/20136/6/20136/6/2013 3:41:10 PMPPASS
call Art with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Corrections made. Rough in ok cover
ELE13-01428 Temporary Service6/6/20136/6/20136/6/2013 3:30:13 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Jim Williams
t/s o/h n ok
ELE13-01432 Permanent Service6/6/20136/6/20136/6/2013 3:01:20 PMPFAIL
Marcus Tam Phone #: ###-####
As per NEC and BCC- For permenant service 2 sources of ground required.
BCC requires an electrical contractor to perform work on any dwelling larger than 2 family.
ELE11-02529 ELE-Aging Inspection6/6/20136/6/20136/6/2013 2:23:34 PM DONE
Still under construction
ELE11-02597 ELE-Aging Inspection6/6/20136/6/20136/6/2013 2:04:31 PM DONE
Still waiting on owner
ELE13-01401 Permanent Service6/6/20136/6/20136/6/2013 1:49:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Jim Williams
p/s o/h rec ok
ELE13-01307 Electrical Rough-In6/6/20136/6/20136/6/2013 1:32:09 PMPPART
Ceiling inspection, existing conduits, and lighting. Cover inspection on small pony wall at serving counter. Please call Mike 1/2 hour prior to inspection. Phone #: ###-#### >>
Inspection requested via web by Mike Basye
Ceiling Fail
BCC Section4-05-32 Code violation not to be retained- When altering a pre-existing electrical wire, equiptment, apparatus, or fixture, or adding any new wiring, the existing electrical wiring in close proximity shall be in accordance with the present code.
BCC Section 4-05-23 Unlawful to conceal- It shall be unlawful for any person to cover up or in any way conceal any electrical wiring, cables, conduits,or other equiptment until the same has been inspected and approved by an electrical inspector.
1/2 wall kitchen rough in ok cover
ELE13-01427 Electrical Rough-In6/6/20136/6/20136/6/2013 1:01:41 PMPPASS
please inspect garage Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS Garage addition rough in ok cover
ELE13-00877 Rough-In Permanent Service6/5/20136/6/20136/6/2013 12:37:26 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
ELE13-00017 Electrical Rough-In6/5/20136/6/20136/6/2013 12:12:50 PMAPASS
3 rooms of floor heat. 25sq. ft ea. per discussion on 6/5 with Rock sometime between 10:30 - 1pm. Phone #: ###-#### >> Inspection requested via web by mike brown
3rd floor bath rooms floor heat rough in ok cover
ELE13-01380 Electrical Rough-In6/5/20136/6/20136/6/2013 10:51:42 AMAPASS
steve has the special key to allow the elevator to get to the 2nd floor, call him when on the way for him to meet you there. thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig wall rough in ok cover
ELE13-01392 Permanent Service6/6/20136/6/20136/6/2013 10:18:01 AMPPASS
mike Phone #: ###-#### p/s u/g n ok
ELE13-01153 Electrical Rough-In6/5/20136/6/20136/6/2013 10:06:49 AMANH
call before for access// Laura Phone #: ###-####
called left message
ELE13-01426 Final6/6/20136/6/20136/6/2013 10:00:56 AMACANC
please call to let me know you are coming so the homeowner can let you in.
thanks Phone #: ###-#### >> Inspection requested via web by Eddy Udry Needed rough in inspection
ELE13-01426 Electrical Rough-In6/6/20136/6/20136/6/2013 9:56:41 AMPPASS
please call to let me know you are coming so the homeowner can let you in.
thanks Phone #: ###-#### >> Inspection requested via web by Eddy Udry Rough in ok cover
ELE13-01298 Rough-In Permanent Service6/6/20136/6/20136/6/2013 9:34:53 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
1. Torn sheathing 14-2 above panel. repair/ repace.
2. Torn sheathing 14-2 up bath light. Repair/ replace.
3. Up bath 12-2 above receptical secured less than 1 1/4" from surface of framing member.
4. Protect wiring within 6' of up stairs attic access.
5. Bond metal tab in all 3/0 boxes.
ELE13-00498 Electrical Rough-In6/5/20136/6/20136/6/2013 8:53:44 AMANH
Contact: Andy Eckhart.... Walls, underground and ceiling inspections please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Called left message