Inspections for the day of: Thursday, June 6, 2013.
Number of inspections: 5
Percentage of inspections complete: 80 %
Percentage of inspections not complete: 20 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02367 FIRE-Final Inspection5/29/20135/30/2013 A 
Contact on site, or Dave at ###-####
FIR13-00133 INSP-Sprinkler Rough-in6/4/20136/6/20136/6/2013 10:28:10 PMAPART
Shell system rough-in completed for the 16th and 17th floors. Noted five areas on the 17th floor and two areas on the 16th floor in need of revision- field changes to piping layout in the remote calc area on the 16th floor, floorplan change on the 17th floor SW corner, missing and obstructed heads at some locations, overspaced coverage at the mens restroom 17th floor. Coverage below ductwork incomplete at this time.
FIR13-00057 INSP-Sprinkler Rough-in6/6/20136/6/20136/6/2013 10:16:33 PMAPART
Fire sprinkler work at the sheetrock soffits in meeting room 301 approved for cover. Plans clouded and dated.
BLD13-01264 FIRE-Final Inspection6/5/20136/6/20136/6/2013 10:12:32 PMAPASS
C/N items finished. Fire life safety finaled.
BLD13-00522 FIRE-Final Inspection6/5/20136/6/20136/6/2013 10:50:03 AMAPASS
Fire life safety inspection passed.