ELE11-02817
| ELE-Aging Inspection | 6/6/2016 | 6/6/2016 | 6/13/2016 10:41:08 AM | | CANC |
|
|
too busy
|
ELE16-01023
| Rough-In Permanent Service | 6/6/2016 | 6/6/2016 | 6/6/2016 3:46:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
|
ELE16-01771
| Rough-In Permanent Service | 6/6/2016 | 6/6/2016 | 6/6/2016 3:31:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in ok cover p/s u/g n ok
|
ELE16-01782
| Electrical Rough-In | 6/6/2016 | 6/6/2016 | 6/6/2016 2:51:20 PM | P | PASS |
|
|
Please call Matt for access ###-#### Phone #: ###-#### Inspection requested via web by Emmet Bushman Rough-in on two outlets ok
|
ELE16-00570
| Electrical Rough-In | 6/6/2016 | 6/6/2016 | 6/6/2016 2:23:16 PM | P | PASS |
|
|
UG Cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Underground for secondary feeds to building ok cover
|
ELE16-01773
| Final | 6/6/2016 | 6/6/2016 | 6/6/2016 2:04:10 PM | P | FAIL |
|
|
Joe Phone #: ###-#### 110.9 available fault current calculation required proir 110.16 Arc flash hazard warning required 400.5 #6 soo cord is rated at 45 amp not 50
|
ELE16-00796
| Final | 6/6/2016 | 6/6/2016 | 6/6/2016 1:25:03 PM | P | FAIL |
|
|
Key is by back door on top of the patio roof Phone #: ###-#### Inspection requested via web by Jason Wicks 406.5 receptacles shall be rigidly mounted 406.4 tamper resistant receptacles required
|
ELE16-01759
| Temporary Service | 6/6/2016 | 6/6/2016 | 6/6/2016 1:09:04 PM | P | PASS |
|
|
Need another one as we had to fix something. Phone #: ###-#### Inspection requested via web by Vicki Moore correction fixed t/s o/h n ok
|
ELE16-01788
| Permanent Service | 6/6/2016 | 6/6/2016 | 6/6/2016 1:08:13 PM | P | PASS |
|
|
Daniel// please call before Phone #: ###-#### t/s o/h rec ok 1 meter needed
|
ELE16-01671
| Temporary Service | 6/6/2016 | 6/6/2016 | 6/6/2016 12:48:52 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder t/s o/h n ok
|
ELE16-01791
| Temporary Service | 6/6/2016 | 6/6/2016 | 6/6/2016 12:32:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Berthelot t/s u/g n ok
|
ELE16-01684
| Electrical Rough-In | 6/6/2016 | 6/6/2016 | 6/6/2016 12:17:54 PM | P | CANC |
|
|
Garage rough in. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown not ready at this time
|
ELE16-01759
| Temporary Service | 6/3/2016 | 6/6/2016 | 6/6/2016 10:14:00 AM | A | FAIL |
|
|
Call Travis with any questions Phone #: ###-#### Inspection requested via web by Vicki Moore 240.24 no over current device shall be located higher then 6'-7" 100 amp breaker not rated where it is installed 110.26 shall maintain 36"working clearences in front of panel need address changed to 1550 W idaho street
|
ELE16-01727
| Rough-In Permanent Service | 6/3/2016 | 6/6/2016 | 6/6/2016 9:17:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough-in ok cover p/s u/g n ok
|
ELE16-01777
| Temporary Service | 6/5/2016 | 6/6/2016 | 6/6/2016 9:08:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
ELE16-01745
| Final | 6/5/2016 | 6/6/2016 | 6/6/2016 8:22:52 AM | A | PASS |
|
|
underground conduit for shop Phone #: ###-#### Inspection requested via web by Mark Morgan needed r/i
|
ELE16-01745
| Electrical Rough-In | 6/6/2016 | 6/6/2016 | 6/6/2016 8:22:35 AM | P | PASS |
|
|
underground conduit for shop Phone #: ###-#### Inspection requested via web by Mark Morgan Underground fro detached shop ok cover
|
ESC15-00354
| Site Final | 6/6/2016 | 6/6/2016 | 6/6/2016 8:15:24 AM | P | PASS |
|
|
site final
|
ESC15-00353
| Site Final | 6/6/2016 | 6/6/2016 | 6/6/2016 8:14:53 AM | P | PASS |
|
|
site final ok
|
ELE15-04080
| Final | 6/6/2016 | 6/6/2016 | 6/6/2016 8:13:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by cal crosby Final ok
|