ELE19-01520
| Final | 6/6/2019 | 6/6/2019 | 6/6/2019 2:45:41 PM | P | FAIL |
|
|
Ready for final Phone #: ###-#### Inspection requested via web by Kevin Oderkirk 210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room 3 receptacles with in 6'.
|
ELE19-02038
| Rough-In Permanent Service | 6/5/2019 | 6/6/2019 | 6/6/2019 2:26:07 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat No concrete encased electrode found, ground rods installed, unerground metal water pipe has been replaced. Rough in ok cover
|
ELE19-02028
| Electrical Rough-In | 6/5/2019 | 6/6/2019 | 6/6/2019 1:30:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Confirmed required receptacles for meeting rooms only 1 large enough for floor receptacles and it needs 2. Walls rough in ok cover
|
ELE18-02742
| Final | 6/5/2019 | 6/6/2019 | 6/6/2019 11:22:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike McCarrel C-4 gibbons exhibit final ok
|
ELE18-03159
| Electrical Rough-In | 6/6/2019 | 6/6/2019 | 6/6/2019 11:07:02 AM | P | CANC |
|
|
Floor heat rough in. The two downstairs bathrooms. Thank you Phone #: ###-#### >> Inspection requested via web by Eric Brown Inspection cancelled from web by: Eric Brown
|
ELE19-00433
| Electrical Rough-In | 6/5/2019 | 6/6/2019 | 6/6/2019 10:59:31 AM | A | CANC |
|
|
Ceiling inspection Phone #: ###-#### Inspection requested via web by Mike McCarrel Hornbill ceiling rough in ok cover
|
ELE19-00769
| Final | 6/5/2019 | 6/6/2019 | 6/6/2019 10:58:44 AM | A | PASS |
|
|
final for bike rack Phone #: ###-#### Inspection requested via web by A.M.E. Office No card posted. Final ok
|
MIS19-00150
| ELE-Conference | 6/5/2019 | 6/6/2019 | 6/6/2019 10:01:21 AM | A | PASS |
|
|
before 10 // Larren Phone #: ###-#### Examined print, no new work found.
|
MIS19-00150
| ELE-Final | 6/6/2019 | 6/6/2019 | 6/6/2019 10:00:27 AM | P | PASS |
|
|
before 10 // Larren Phone #: ###-#### No new electrical work found. Final ok
|
ELE19-00596
| Final | 6/5/2019 | 6/6/2019 | 6/6/2019 9:32:16 AM | A | PASS |
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden No card posted. Final ok
|