Inspections for the day of: Wednesday, June 7, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDixie Fellows
TitleMEC-COM/RES INSPECTOR
Phone #794-6208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC06-01495 Conference6/7/20066/7/20066/8/2006 8:37:34 AMPPEND
Phone #: ###-#### Internet Inspection Request from: Stacy Ware..spoke with engineer regarding fire protection issues..all existing duct detectors were installed in supply duct under the 97 umc? short of gutting and changing all existing ductwork i suggested asking engineer to install a duct detector in the supply side of existing furnace that had no detector at all..the reason for this is the r/a isn't ducted and open to all other spaces. i called forrest and asked him to meet me at job, so he could look at issues from the fire inspection side..i then discussed the lack of fresh air into space required by building and mechanical code.
MEC06-01815 Conference6/6/20066/7/20066/8/2006 8:27:22 AMAPASS
nat - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley...discussed ducts, range and dryer vent terminations..i asked nat to let g/c know about clearance requirement around gas stove to cabinets and other combustibles..
MEC06-01835 Final6/7/20066/7/20066/7/2006 3:55:32 PMPPASS
Please call with any questions; Phone #: ###-#### Internet Inspection Request from: Sonja Hankel
MEC06-01836 Final6/7/20066/7/20066/7/2006 3:55:06 PMPPASS
Please call with any questions; Phone #: ###-#### Internet Inspection Request from: Sonja Hankel
MEC06-01806 Final6/7/20066/7/20066/7/2006 3:10:20 PMPPASS
MEC06-01806 Pressure Test6/7/20066/7/20066/7/2006 3:09:40 PMPPASS
joe ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie..60lb ok
MEC06-01742 Final6/7/20066/7/20066/7/2006 3:07:17 PMPPASS
FRONT DOOR UNLOCKED. FURNACE IS IN CRAWL SPACE USE FRONT CRAWL ACCESS TO GET TO FURNACE; Phone #: ###-#### Internet Inspection Request from: Stacy Ware
MEC06-00578 Final6/7/20066/7/20066/7/2006 12:29:37 PMPFAIL
###-####..posted corrections..talked to contractor
MEC06-01738 Rough-in6/7/20066/7/20066/7/2006 12:28:47 PMAPEND
Scheduled by a contractor via Hello! on 6/7/2006 at 7:12:32 AM. Contact: ###-####...met with kevin..need manuf ok for f/p to be set back in so far
MEC06-00578 Final6/6/20066/7/20066/7/2006 8:53:10 AMANR
late am??? dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie..will give cont more time to finish exhaust