Inspections for the day of: Wednesday, June 7, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS06-00136 FIR-Final6/7/20066/7/20066/7/2006 5:25:24 PMPFAIL
Provide tag for the fire extinguisher, repair the three emergency lights and the exit sign at the walk through area
BLD05-02957 FIRE-Final Inspection6/7/20066/7/20066/7/2006 5:24:01 PMPFAIL
Need to provide a exit/emergency light as shown on the approved plans and final the fire alarm permit.
BLD06-00531 FIRE-Conference6/6/20066/7/20066/7/2006 5:23:12 PMADONE
I told John that I was not concerned about the open area of the ceiling and that it appears that the duct smoke detectors are not going to be required.
BLD05-02094 FIRE-Final Inspection6/7/20066/7/20066/7/2006 3:34:23 PMPFAIL
Need to final the shell permit, tag the fire extinguisher and either test the duct smoke detetors or remove them since they are not required per code.
BLD05-03473 FIRE-Final Inspection6/7/20066/7/20066/7/2006 2:42:20 PMPPASS
Life safety finaled
FIR06-00065 INSP-Sprinkler Rough-in/Hydro6/6/20066/7/20066/7/2006 2:16:06 PMAPART
Above ground hydro test passed. Sprinkler rough-in failed due to the upright sprinkler heads not meeting NFPA 13 8.6.5.2.1.6 and 8.6.5.2.1.7. Also the sprinkler heads are overspaced at the west end of the sprinkler system.
FIR06-00118 INSP-Final Inspection6/6/20066/7/20066/7/2006 11:09:36 AMAFAIL
No test performed due to a 15cd a/v missing in corridor 107 that is shown on the approved plans.
FIR06-00314 INSP-Sprinkler Rough-in/Hydro6/6/20066/7/20066/7/2006 8:57:33 AMAPASS
Sprinkler rough-in passed. Some of the drops are overspaced by a few inches. These sprinklers are on 15' long drops which once tile is in may be spaced correctly. This will be checked at final.
FIR06-00044 INSP-Final Inspection6/6/20066/7/20066/7/2006 8:55:11 AMAPASS
Permit finaled