ELE07-01763
| Final | 6/7/2007 | 6/7/2007 | 6/7/2007 3:21:43 PM | P | PASS |
|
|
corrections are done Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok survey posted called 406.8 inuse covers
|
ELE07-02055
| Electrical Rough-In | 6/6/2007 | 6/7/2007 | 6/7/2007 2:34:19 PM | P | PART |
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Victoria u/g between blds ok
|
ELE07-01947
| Temporary Service | 6/7/2007 | 6/7/2007 | 6/7/2007 2:02:21 PM | P | PASS |
|
|
Temporary Power - Thank you!! (overhead) Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s o/h new ok
|
ELE06-03162
| Final | 6/7/2007 | 6/7/2007 | 6/7/2007 1:35:14 PM | P | FAIL |
|
|
key in outlet box by man door. Internet Inspection Request from: Shane Vigil corr. new violations created, 110.3(B) & 314.3 manufactures instructions , and metallic flex not allowed in plastic boxes, BCC wiring shall be remove if box is blacked off where fiis removed in MB closet
|
ELE07-01265
| Electrical Rough-In | 6/7/2007 | 6/7/2007 | 6/7/2007 12:55:50 PM | P | PART |
|
|
concrete cover for electrode ok
|
ELE07-01264
| Rough-In Permanent Service | 6/6/2007 | 6/7/2007 | 6/7/2007 12:45:37 PM | A | PASS |
|
|
Journeyman on site; Gene ###-####. Thank you! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i p/s u/g new ok
|
ELE07-01482
| Permanent Service | 6/6/2007 | 6/7/2007 | 6/7/2007 11:00:17 AM | A | FAIL |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Hattie James called corr, not made still needs to remove bush, and stump
|
ELE07-02058
| Electrical Rough-In | 6/6/2007 | 6/7/2007 | 6/7/2007 10:31:12 AM | A | PASS |
|
|
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
ELE07-02058
| Final | 6/7/2007 | 6/7/2007 | 6/7/2007 10:30:51 AM | A | PASS |
|
|
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
ELE07-02060
| Rough-In Permanent Service | 6/6/2007 | 6/7/2007 | 6/7/2007 10:07:47 AM | A | FAIL |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr called210.52(A&B) needs recept outlet kit wall by pantry, 312.5 no SER allowed in conduit out of bottom of panel, 334.23 protect cables by attic access, 334.30 remove cable loop and staple within 12" vacuum outlets, 314.17(C) replace all 2,3,4, gang boxes with broken out factory clamps,
|
ELE06-02704
| Electrical Rough-In | 6/6/2007 | 6/7/2007 | 6/7/2007 8:53:30 AM | A | PART |
|
|
Please inspect "ceiling cover" on all 3 floors of C-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok anop
|
ELE07-02054
| Permanent Service | 6/6/2007 | 6/7/2007 | 6/6/2007 2:37:26 PM | A | PASS |
|
|
###-#### - dan p/s o/h rec. ok
|