Inspections for the day of: Thursday, June 7, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03238 FIRE-Final Inspection6/6/20076/7/20076/11/2007 9:49:48 PMPPASS
Fire life safety finaled, emergency light functionality verified per letter of compliance submitted by the electrical contractor.
FIR07-00233 INSP-Sprinkler Rough-in/Hydro6/5/20076/7/20076/11/2007 1:37:45 PMAFAIL
Missing proper hangers at the FDC piping, one utility room pendent is missing a hanger, need correct temp. SW head at a first floor bedroom, piping at two locations adjacent to the 1st floor carports are subject to freeze potential as installed, missing head at the riser, overspaced heads at the 2nd floor in three units, need to verifiy tenting prior to approval for cover.
FIR06-00755 INSP-Sprinkler Rough-in/Hydro6/7/20076/7/20076/8/2007 11:57:35 AMPPART
UG hydrostatic test of the fire supply line to the east building passed.
BLD07-00660 FIRE-Final Inspection6/7/20076/7/20076/8/2007 10:04:57 AMPPASS
Life safety inspection passed, one additional fire extinguisher mounted on the wall while on site.
FIR05-00752 INSP-Final Inspection6/5/20076/7/20076/7/2007 3:09:59 PMANR
Pending hood suppression tie in.
BLD07-00399 FIRE-Final Inspection6/7/20076/7/20076/7/2007 2:23:39 PMPPASS
Fire life safety is satisfactory, inspection passed.
BLD06-03461 FIRE-Final Inspection6/7/20076/7/20076/7/2007 2:16:27 PMPPASS
Correction notice items are complete, fire life safety inspection passed.
FIR06-00007 INSP-Final Inspection6/6/20076/7/20076/7/2007 1:45:21 PMACANC
No time available for this inspection today.
BLD06-03461 FIRE-Final Inspection6/6/20076/7/20076/7/2007 1:42:55 PMAFAIL
Wrong permit number called in for inspection, was intended for an FIR #.
FIR07-00494 INSP-Final Inspection6/6/20076/7/20076/7/2007 1:26:59 PMAPASS
Fire alarm work passed final inspection, permit finaled.
FIR07-00287 INSP-Final Inspection6/7/20076/7/20076/7/2007 1:24:55 PMPCANC
rod -5th floor ste 520; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
FIR07-00230 INSP-Sprinkler Rough-in/Hydro6/6/20076/7/20076/7/2007 1:24:12 PMPPART
OH hydrostatic test passed inspection, UG hydro lost 4psi. during two hour test.
FIR07-00230 INSP-Sprinkler Rough-in/Hydro6/6/20076/7/20076/7/2007 1:22:28 PMAPART
OH rough-in is acceptable.
FIR06-00728 INSP-Final Inspection6/1/20076/7/20076/7/2007 10:38:13 AMANR
Per phone call from the contractor, project is not ready for final due to related alarm work issues.
FIR06-00985 INSP-Sprinkler Rough-in6/6/20076/7/20076/7/2007 10:31:34 AMADEFR
Inspection rescheduled in conjunction with an OH hydro on 6/11 per phone call from contractor.
FIR06-01019 FIR-Aging Inspection6/7/20076/7/20076/7/2007 10:29:20 AM DONE
Work in progress.
FIR07-00193 INSP-Sprinkler Rough-in/Hydro6/5/20076/7/20076/5/2007 9:38:41 AMACANC
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett