BLD06-03238
| FIRE-Final Inspection | 6/6/2007 | 6/7/2007 | 6/11/2007 9:49:48 PM | P | PASS |
|
|
Fire life safety finaled, emergency light functionality verified per letter of compliance submitted by the electrical contractor.
|
FIR07-00233
| INSP-Sprinkler Rough-in/Hydro | 6/5/2007 | 6/7/2007 | 6/11/2007 1:37:45 PM | A | FAIL |
|
|
Missing proper hangers at the FDC piping, one utility room pendent is missing a hanger, need correct temp. SW head at a first floor bedroom, piping at two locations adjacent to the 1st floor carports are subject to freeze potential as installed, missing head at the riser, overspaced heads at the 2nd floor in three units, need to verifiy tenting prior to approval for cover.
|
FIR06-00755
| INSP-Sprinkler Rough-in/Hydro | 6/7/2007 | 6/7/2007 | 6/8/2007 11:57:35 AM | P | PART |
|
|
UG hydrostatic test of the fire supply line to the east building passed.
|
BLD07-00660
| FIRE-Final Inspection | 6/7/2007 | 6/7/2007 | 6/8/2007 10:04:57 AM | P | PASS |
|
|
Life safety inspection passed, one additional fire extinguisher mounted on the wall while on site.
|
FIR05-00752
| INSP-Final Inspection | 6/5/2007 | 6/7/2007 | 6/7/2007 3:09:59 PM | A | NR |
|
|
Pending hood suppression tie in.
|
BLD07-00399
| FIRE-Final Inspection | 6/7/2007 | 6/7/2007 | 6/7/2007 2:23:39 PM | P | PASS |
|
|
Fire life safety is satisfactory, inspection passed.
|
BLD06-03461
| FIRE-Final Inspection | 6/7/2007 | 6/7/2007 | 6/7/2007 2:16:27 PM | P | PASS |
|
|
Correction notice items are complete, fire life safety inspection passed.
|
FIR06-00007
| INSP-Final Inspection | 6/6/2007 | 6/7/2007 | 6/7/2007 1:45:21 PM | A | CANC |
|
|
No time available for this inspection today.
|
BLD06-03461
| FIRE-Final Inspection | 6/6/2007 | 6/7/2007 | 6/7/2007 1:42:55 PM | A | FAIL |
|
|
Wrong permit number called in for inspection, was intended for an FIR #.
|
FIR07-00494
| INSP-Final Inspection | 6/6/2007 | 6/7/2007 | 6/7/2007 1:26:59 PM | A | PASS |
|
|
Fire alarm work passed final inspection, permit finaled.
|
FIR07-00287
| INSP-Final Inspection | 6/7/2007 | 6/7/2007 | 6/7/2007 1:24:55 PM | P | CANC |
|
|
rod -5th floor ste 520; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
FIR07-00230
| INSP-Sprinkler Rough-in/Hydro | 6/6/2007 | 6/7/2007 | 6/7/2007 1:24:12 PM | P | PART |
|
|
OH hydrostatic test passed inspection, UG hydro lost 4psi. during two hour test.
|
FIR07-00230
| INSP-Sprinkler Rough-in/Hydro | 6/6/2007 | 6/7/2007 | 6/7/2007 1:22:28 PM | A | PART |
|
|
OH rough-in is acceptable.
|
FIR06-00728
| INSP-Final Inspection | 6/1/2007 | 6/7/2007 | 6/7/2007 10:38:13 AM | A | NR |
|
|
Per phone call from the contractor, project is not ready for final due to related alarm work issues.
|
FIR06-00985
| INSP-Sprinkler Rough-in | 6/6/2007 | 6/7/2007 | 6/7/2007 10:31:34 AM | A | DEFR |
|
|
Inspection rescheduled in conjunction with an OH hydro on 6/11 per phone call from contractor.
|
FIR06-01019
| FIR-Aging Inspection | 6/7/2007 | 6/7/2007 | 6/7/2007 10:29:20 AM | | DONE |
|
|
Work in progress.
|
FIR07-00193
| INSP-Sprinkler Rough-in/Hydro | 6/5/2007 | 6/7/2007 | 6/5/2007 9:38:41 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|