Inspections for the day of: Thursday, June 7, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00690 FIR-Aging Inspection6/7/20126/7/20126/8/2012 5:34:25 PM PEND
In progress
FIR12-00108 INSP-Sprinkler Rough-in6/6/20126/7/20126/8/2012 5:30:48 PMPPART
Partial inspection for cover at areas completed to date 2nd floor only. Corrections include hanger attatchment at the breakroom, install does not match plan at the storage and mens restroom (four heads are supplied from 1" pipe), noted work completed in hatched plan areas at locations indicated as not affected, missing hanger above the permits desk. Cover at rooms approved where clouded and dated.
FIR12-00241 INSP-Sprinkler Rough-in6/7/20126/7/20126/8/2012 5:22:31 PMAPEND
BLD12-01321 FIRE-Final Inspection6/7/20126/7/20126/8/2012 5:21:27 PMANR
BLD11-02317 FIRE-Conference6/7/20126/7/20126/8/2012 5:20:42 PMADONE
Regarding second floor cover inspections.
BLD11-02976 FIRE-Final Inspection6/6/20126/7/20126/8/2012 6:52:19 AMAPASS
C/N items field verified for completion. Fire life safety inspection passed.