Inspections for the day of: Friday, June 7, 2013.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE13-00089 GCE-Rough-In6/7/20136/7/20136/10/2013 9:09:59 AMPPASS
Mike ###-#### 4 light pole bases and underground rough in ok cover
GCE13-00092 GCE-Permanent Service6/7/20136/7/20136/10/2013 8:39:35 AMPFAIL
Ron ###-#### Minimum burial depth 12" if GFCI protected,18" if not GFCI protected, 2" below concrete.
ELE12-00213 ELE-Aging Inspection6/7/20136/7/20136/7/2013 4:03:14 PM DONE
still under construction
ELE13-01438 Final6/7/20136/7/20136/7/2013 3:53:04 PMPCANC
This site is in the north east corner of the Key Bank property, in the grass near the Idaho Power padmount transformer.
Thanks !!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
Final ok
ELE13-01438 Rough-In Permanent Service6/7/20136/7/20136/7/2013 3:43:46 PMPPASS
This site is in the north east corner of the Key Bank property, in the grass near the Idaho Power padmount transformer.
Thanks !!! Dan. Phone #: ###-#### >>
Inspection requested via web by Dan Mitchell
Rough in ok cover p/s u/g n ok
MIS13-00160 ELE-Conference6/7/20136/7/20136/7/2013 2:50:31 PMPDONE
complaint "Sprint" (not Verizon/Towercom Technologies) is doing work without permit on SW corner of property. Please call property mangaer to meet you out there, Tom Lavoie ###-####. Reference permit # ELE13-00872 for work performed up to this date.
ELE13-01153 Electrical Rough-In6/7/20136/7/20136/7/2013 2:39:34 PMPPASS
Please call ahead for access - laura Phone #: ###-#### Addition rough in ok cover
ELE12-03105 ELE-Request for Extension6/7/20136/7/20136/7/2013 1:56:56 PMPPASS
brent Phone #: ###-#### Extension ok
ELE13-01027 Rough-In Permanent Service6/3/20136/7/20136/7/2013 1:52:42 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Craig Korell Addition bedroom rough in ok cover p/s o/h rec ok
ELE13-01431 Electrical Rough-In6/7/20136/7/20136/7/2013 1:33:27 PMPPASS
Kitchen refer wall and stair walls rough in ok cover
ELE13-01440 Temporary Service6/7/20136/7/20136/7/2013 1:00:10 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by George Pascua
110.26 Minimum work space of 30" wide not available on side of transformer where placed
MIS13-00161 ELE-Conference6/7/20136/7/20136/7/2013 12:31:06 PMPDONE
doing electrical and framing work without permit.
Made contact with owner who admitted doing work himself
ELE12-03075 Conference6/7/20136/7/20136/7/2013 10:50:57 AMADONE
Rock, need you to stop by and talk to owner and myself about exterior heat mat installation under pavers. Thanks. Darrin Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Discussed code requirements for snow melt mats under pavers
ELE13-01418 Conference6/7/20136/7/20136/7/2013 10:24:58 AMPDONE
scott Phone #: ###-#### Discussed overcurrent protection, code requirements for kitchen remodel, and termination of knob and tube wiring.
ELE13-01436 Electrical Rough-In6/6/20136/7/20136/7/2013 10:00:36 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
Kitchen remodel rough in ok cover
ELE12-00530 Final6/6/20136/7/20136/7/2013 9:28:24 AMAPASS
Phone #: 3452982 >> Inspection requested via mobile web by Christen carlson Final ok
ELE12-00530 Electrical Rough-In6/7/20136/7/20136/7/2013 9:26:51 AMPPASS
Phone #: 3452982 >> Inspection requested via mobile web by Christen carlson
Sign UL listing confirmed rough in ok
ELE13-01298 Rough-In Permanent Service6/6/20136/7/20136/7/2013 9:23:28 AMAPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
Rough in ok cover p/s u/g n ok