ELE17-01189
| Final | 6/7/2017 | 6/7/2017 | 6/7/2017 1:08:36 PM | P | PASS |
|
|
There should be someone there. If you have any questions please call Calvin ###-#### Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
ELE17-01339
| Final | 6/7/2017 | 6/7/2017 | 6/7/2017 1:07:33 PM | P | PASS |
|
|
There should be someone there. If you have any questions please call Calvin ###-#### thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
|
ELE17-01652
| Electrical Rough-In | 6/7/2017 | 6/7/2017 | 6/7/2017 12:16:50 PM | P | PASS |
|
|
Correction made Upstairs, OK to cover
|
ELE17-01751
| Rough-In Permanent Service | 6/6/2017 | 6/7/2017 | 6/7/2017 11:31:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
ELE17-00943
| Final | 6/6/2017 | 6/7/2017 | 6/7/2017 10:36:53 AM | A | PASS |
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk final ok
|
ELE17-01652
| Electrical Rough-In | 6/6/2017 | 6/7/2017 | 6/7/2017 10:12:40 AM | A | FAIL |
|
|
Ready for cover inspection for upstairs Phone #: ###-#### Inspection requested via web by Kevin Oderkirk 406.9C Receps shall not be locate above tub.
|
ELE16-03972
| Final | 6/6/2017 | 6/7/2017 | 6/7/2017 9:27:58 AM | A | FAIL |
|
|
Bob Phone #: ###-#### 440.22C. A/C overcurrent protection shall not exceed nameplate rating. 406.12A All dwelling unit receps shall be tamper resistant.(Kitchen and Bath GFCI receps) Missing lights in bed and Back patio. Out door recep by A/C Dead. 410.12 Closet Storage space. Lights shall not be installed within 12in of edge of shelf. Strap liquidtight below A/C with listed straps
|