BLD18-02795
| FIRE-Final Inspection | 6/7/2019 | 6/7/2019 | 6/7/2019 3:09:16 PM | P | FAIL |
|
|
Provide sign offs for the project related fire sprinkler and fire alarm permits, Provide emergency light for the Fire Pump Room, Provide testing/inspection for the elevator, Provide singage for the Fire Pump/Riser Room.
Chad- Phone #: ###-####
|
GRD18-00064
| FIRE-Final Inspection | 6/7/2019 | 6/7/2019 | 6/7/2019 3:07:20 PM | P | FAIL |
|
|
Provide "No Parking Zone" at space i front of the north fire hydrant, Provide fire dept/plan review approval for modified fire dept access road.
|
BLD19-01995
| FIRE-Final Inspection | 6/7/2019 | 6/7/2019 | 6/7/2019 1:57:07 PM | P | PASS |
|
|
life safety passed
Call to meet // Gary Phone #: ###-####
|
FIR18-00809
| INSP-Alarm Testing | 6/7/2019 | 6/7/2019 | 6/7/2019 1:26:12 PM | P | DONE |
|
|
Need the interconnections with the fire sprinkler/fire pump devices tested, need elevator recall tested. Need duct smoke detectors tested. It appears the sync issue is actually an echo from the concrete floors and large open spaces. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR18-00916
| INSP-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 1:24:41 PM | P | CANC |
|
|
Still need the underground supply line hydro passed and the valve added on the discharge side of the pump. Need devices tested with the Fire Alarm Control Panel.
Contact Andrew Larson ###-#### 30 min prior to fire final insp start please.
Thank you Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00913
| INSP-Sprinkler Rough-in/Hydro | 6/6/2019 | 6/7/2019 | 6/7/2019 1:23:14 PM | A | CANC |
|
|
The underground supply piping is still losing pressure. Was not able to start a test.
Contact Andrew Larson ###-#### 30 min prior to UG Hydro start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF19-00034
| INSP-Final | 6/6/2019 | 6/7/2019 | 6/7/2019 12:31:29 PM | A | DONE |
|
|
Life safety passed
Call prior to going Phone #: 4056425898 >> Inspection requested via mobile web by Michael
|
BLD19-00139
| FIRE-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 12:14:35 PM | A | CANC |
|
|
Will be ok to final life safety when the project related fire alrm permit has been finaled.
Troy,
Call me when you get a moment before you head over to the space.
Thanks,
Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|
FIR19-00239
| INSP-Final Inspection | 6/7/2019 | 6/7/2019 | 6/7/2019 10:27:41 AM | A | PASS |
|
|
Permit finaled.
mike oswald Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR19-00239
| INSP-Sprinkler Rough-in | 6/7/2019 | 6/7/2019 | 6/7/2019 10:27:20 AM | A | PASS |
|
|
mike oswald Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD18-04307
| FIRE-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 10:24:47 AM | A | FAIL |
|
|
Provide fire extinguisher and emergency lighting as per the approved plans.
Kenny Phone #: ###-####
|
BLD19-00845
| FIRE-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 9:45:45 AM | A | PASS |
|
|
Life safety passed
Requested by Shane Treasure Phone #: ###-#### Inspection requested via web by Shane Treasure
|
FIR19-00312
| INSP-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 9:45:06 AM | A | PASS |
|
|
Permit finaled
Nick Phone #: ###-####
|
NAF19-00042
| INSP-Final | 6/6/2019 | 6/7/2019 | 6/7/2019 9:22:37 AM | A | DONE |
|
|
Permit finaled. Suppression system function witnessed.
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
|
FIR18-00809
| INSP-Alarm Testing | 6/6/2019 | 6/7/2019 | 6/7/2019 8:12:16 AM | A | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 07, 2019.
|
NAF19-00042
| INSP-Sprinkler Rough-in/Hydro | 6/6/2019 | 6/7/2019 | 6/6/2019 2:10:29 PM | A | CANC |
|
|
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson Inspection cancelled via mobile web on Thursday, June 06, 2019.
|
FIR18-00809
| INSP-Alarm Testing | 6/6/2019 | 6/7/2019 | 6/6/2019 11:20:40 AM | P | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 06, 2019.
|